4. Installation
4.5 Assembling the AC Connector
. 14.
There are two AC terminals and the assembly steps for both are the same.
Take out the AC connector parts from the packaging.
1. Make sure you use a cable within the correct specifications as shown in the image below.
Describe
Numerical value
Wire diameter
10-12mm
Traverse cross sectional area
2.5-6mm
2
Exposure Length
12mm
2. Lead the AC cable through the cable gland and the housing.
3. Remove a length of 40mm of the cable jacket and strip the wire insulation to a length of
8-15mm.
4. Installation
4. Each of the terminals are labeled. Ensure that the correct conductor is fastened
(1.2 N.m. torque) to the correct terminal.
WARNING:
Observe the terminal layout of terminal block.
Do not connect the phase lines to "PE" terminal, otherwise the inverter will not
function properly.
5. Make sure the rib of the terminal block and the groove on the housing engage perfectly
until a "click" is heard to felt.
.15 .