NOTE: Use kit A to upgrade to electric actuator!
1. Find the screw and remove the cover! Find the 2 hex screws located on the board of
mechanism, unscrew them and remove manual mechanism.
2. Find the 2 hex screws located on the transition board
(B),
unscrew them and replace FA
transition plate
(A)
with BE transition plate.
NOTE: Pay attention to the position of indication cut on the BE transition plate.
3. Insert the rubber plug into the opening for the thermal fuse. Install the Belimo actuator
and fasten it with screws (2 hexagon screws M6 x 55).
4. Drill hole (Ø 16 mm) for the fuse of Belimo mechanism and fix it with self-tapping screws.
NOTE: Install the thermal fuse in a place where it will not interfere with the operation of
the damper blade!
Test the operation of the damper blade!
UPGRADE TO ELECTRIC ACTUATOR
MANUAL R25 <-> BELIMO
d100-d315
The blade must be closed before replacement the mechanism.
B
A
1
2
3
4
Video instruction
https://www.youtube.com/watch?v=t54DTocVKDs&feature=youtu.be