Installation and Operation Manual (Rev E)
SGI Series Inverters
DOCR-060371
18
4.2
Equipment Grounding Conductor (EGC)
The ground bond plate is also equipped with a number of provisions for equipment grounding
conductors. In most instances, these will be used for the equipment grounds originating at the
combiner boxes used to feed the subcombiner positions within the inverter.
Figure 4.2 - EGC Lug Positions
Cu or Al Conductors
Max. 28 x 14AWG-1/0AWG
75C connections, 50 in-lbs
1 wire per lug position