Troubleshooting
9 Troubleshooting
This section contains information and procedures for solving possible
problems with A1-HYB-G2 inverters, and provides you with troubleshooting
tips to identify and solve most problems that could occur with A1-HYB-G2
series inverters.
AFD Self Check Fault
Arc Detect Fault
Bat Relay Fault
Battery Relay Fault
Please contact SolaX Technical Support
PV Conn Dir Fault
PV Reverse Connection Fault
• Re-connect the PV correctly
Battery Volt Fault
Battery Voltage Over high or Over low Fault
• Check if the battery input voltage is within the normal range
• Please contact SolaX Technical Support
EPO Fault
EPO Activated or Inverter Emergency Off
BI Comm Fault
Communication Fault between Inverter and BI
• Check if the RS485 communication cable of BI connects to
communication board of inverter.
• Please contact SolaX Technical Support
AFDI Model Self Check Fault
• Please check if the AFDI module connects normally
• Or contact SolaX Technical Support
DC Arc occurs or DC Arc Check Fault
• Please check if there is any visible arc vestige firstly
• Clear the PV input and solar battery board connects normally
• If Arc is detected five times in one hour, please manually clear Arc.
Otherwise, it will re-connect to grid in five minutes
Faults
Diagnosis and solution
Troubleshooting
65
Update File Fail
File Upgrade Fault
• Check if the file and the folder are correct
• Please contact SolaX Technical Support
Udisk Update Fault
U Disk Upgrade Fault
• Check if the U disk is correctly plugged and the file is correct
• Please contact SolaX Technical Support
Meter Fault
Meter Communication Fault
• Check if the communication cable between inverter and BI
connects normally or contact SolaX Technical Support
BMS_Lost
Update Fault
Software Upgrade Fault
• Check if the communication cable between inverter and BI and
re-upgrade the software
• Check the communication cable between control board and
communication board and re-upgrade the software
• Check the communication cable between inverter and battery
• Or contact SolaX Technical Support
Version Mismatch
Software Version Mismatch
• Check the software version of control board and communication
board
PV Volt Fault
PV Voltage Out of Normal Range
•Decrease the PV voltage
•Or contact SolaX Technical Support
DCI OCP Fault
DCI over current protection Fault
• Please SolaX Technical Support
DCV OVP Fault
DCV EPS over voltage protection Fault
• Please SolaX Technical Support
BMS Communication Lost
• heck the communication connection between the
C
battery and the inverter
Faults
Diagnosis and solution
64
This section will help you narrow down the source of any problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on the System Control Panel or Fault codes on
the inverter information panel. If a message is displayed, record it before doing
anything further.
Bat Current
Imbalance
The Firmware Fault of Battery Charge
• Please contact SolaX Technical Support
Bat ConDir Fault
The Positive and Negative Pole of Battery Connected Reversely
• Re-connect the battery.