INSTALLATION AND OPERATION MANUAL, ELECTRIC CONVECTION STEAMER,
SX-34EC, SX-55EC, SX-34EO, SX-55EO
PART NUMBER 10079R2
7 2003-05-13
INSTALLATION INSTRUCTIONS
(Continued)
WARNING: Disconnect the power supply to the appliance before
cleaning or servicing.
Make electrical connection through the 1-1/8" (29 mm) diameter hole provided using 3/4" (19
mm) trade size conduit. Refer to the wiring diagram located inside the right side panel. Use
90°C minimum insulated wire.
PLUMBING CONNECTIONS
WARNING: Plumbing connections must comply with applicable
sanitary, safety, and plumbing codes.
The water supply inlets are provided with 3/8" (10 mm) compression fittings for 3/8" O.D.
copper tubing. The water supply line pressure should be 25 - 50 psi (170 - 345 kPa) for each
line. The water supply to the generator tank is separate from the water supply to the cooling
system where steam is condensed before entering the drain line.
Install line strainers (not provided). A manual shutoff valve for each supply line must be
provided convenient to the steamer.
We recommend treated water feeding the boiler inlet supply, and untreated water feeding the
cooling system inlet. Hook-ups are labelled on the back of the steamer.