7 DHW heating
DHW tank operating mode
3
Always off
: The DHW tank charge pump is switched
off permanently.
Exception for frost protection mode: The DHW tank
charging pump is activated if
- the outside temperature is <2°C, and
- the DHW tank temperature falls to <10°C.
Always on
: The DHW tank charge pump is switched
on permanently. The pump is controlled taking the
parameters
Required temperature 1, Minimal tem-
perature
and
Hysteresis
into account.
Time switches (
Monday-Sunday, daily
, etc.): different
time ranges can be set, in which the DHW tank
charge pump is switched to
ON
.
i
The operating mode
Monday - Sunday
is not
available if you are using the
mySOLARFOCUS app
.
7.2 Fresh water module - FWM (optional)
A fresh water module heats domestic hot water in cir-
culation operation. The circulation pump of the fresh
water module starts if a DHW extraction point (also
called a
tapping point
e.g. shower or bath) is opened.
The energy for heating up domestic hot water is taken
from the upper area (called the
DHW area
) of the buf-
fer tank.
Abb. 2-34
1 Buffer tank temperature
2 Required DHW temperature
3 Speed of the fresh water module pump
4 Recirculation temperature
[1](only visible if a recir-
culation sensor is connected)
5 Start recirculation pump
[1](serves for immediate
start of the recirculation pump)
6 Circulation pump settings
[1]
7 Fresh water module settings
8 Fresh water module status line
[1] The recirculation control is an optional additional func-
tion.
Fresh water module settings
7
Pump control
Always off
: The fresh water module pump is per-
manently switched off; no domestic hot water is hea-
ted up.
Always on
: (= manual mode); the fresh water module
pump is always switched on.
Automatic
(= default setting), the fresh water module
pump starts when a flow is detected in the pipework
by an electronic sensor (e.g. the tap is opened at a
connected device).
Required DHW temperature
This parameter is only active for the release type
Automatic
. The fresh water module regulates the tem-
perature at which the connected hot water devices
receive water to this temperature.
24
Operation manual
vampair