![SolarEdge L20-IB00 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/solaredge/l20-ib00/l20-ib00_user-manual_1313773057.webp)
48
L20, L30
OUTPUT dry contact:
Contains a total of 4 output dry contacts. User can choose different
function for OUT 01~04. And choose Normally Closed/ Normally Opened, the default value
is Normally opened.
Each dry contact has 16 functional options, including UPS Warning, Online Mode,
Battery Mode, Bypass Mode, INV Overload, Fan Fault, BATT Fault, BATT Disconnect,
BATT Low Volt, Mains Abnormal, BYP Not Available, EPO, Maint Mode, Parallel Comm
Fault, ECO Mode, Close.
OUT 01:
The default value is UPS Warning.
OUT 02:
The default value is Bypass Mode.
OUT 03:
The default value is BATT Low Volt.
OUT 04:
The default value is Online Mode.
NOTE!
Each output dry contact can be N.O or N.C.
Содержание L20-IB00
Страница 2: ......
Страница 17: ...9 L20 L30 3 4 Cabinet view Figure 1 Front view Side view of L20 and L30...
Страница 36: ...27 L20 L30 4 3 4 1 Main Click the main block to enter the main data display window...
Страница 38: ...29 L20 L30 4 3 4 4 Battery Click the battery block to enter the battery data display window...
Страница 39: ...30 L20 L30 4 3 4 5 Status info Click the Status info to enter the Status info display window...
Страница 40: ...31 L20 L30...
Страница 58: ...49 L20 L30 4 3 8 Maintenance Touch correction and battery self test...
Страница 60: ...51 L20 L30 4 3 8 4 Cycle mode Modify the check date time and check time 10S default 10min EOD...
Страница 64: ...55 L20 L30...
Страница 81: ......