44
L20, L30
Cabinet Parallel Basic Units:
Parallel cabinet number, must modify the total parallel
cabinet number after setting work mode to parallel mode. The value can only be 2,
because only two UPS systems of this model can be connected in a parallel system.
Cabinet Parallel Redundancy Units:
Parallel redundancy cabinet number, can modify
the redundancy cabinet number after set work mode to parallel mode. The value canbe
0~1, default value is 0, maximum allowed value is 1, because only two UPS systems of
this model can be connected in a parallel system.
4.3.7.3.
Output setting
Output Freq:
Output frequency. The value can be 50Hz or60Hz.
Output Volt Level:
Output voltage level. The value can be 220, 230 and240.
Output Volt Adjust (%):
Inverter voltage regulated. The value can be -5%~0~+5%, step
is 0.5%, default value: 0.
Содержание L20-IB00
Страница 2: ......
Страница 17: ...9 L20 L30 3 4 Cabinet view Figure 1 Front view Side view of L20 and L30...
Страница 36: ...27 L20 L30 4 3 4 1 Main Click the main block to enter the main data display window...
Страница 38: ...29 L20 L30 4 3 4 4 Battery Click the battery block to enter the battery data display window...
Страница 39: ...30 L20 L30 4 3 4 5 Status info Click the Status info to enter the Status info display window...
Страница 40: ...31 L20 L30...
Страница 58: ...49 L20 L30 4 3 8 Maintenance Touch correction and battery self test...
Страница 60: ...51 L20 L30 4 3 8 4 Cycle mode Modify the check date time and check time 10S default 10min EOD...
Страница 64: ...55 L20 L30...
Страница 81: ......