40
L20, L30
Bypass Switches Limit:
Cross currents occur during the transfer between bypass mode and
normal mode, which impacts the system. This parameter specifies the number of transfers
between bypass mode and normal mode within 1 hour, which ensures system security. The
value can be 3 to 10 and is 10 by default.
EPO Transfers To BYP:
Specifies whether transfers to bypass mode when press EPO button.
The default value is Disable.
4.3.7.
Advanced settings
Click advanced setting, input the correct password. The user password is “499283”.