43
L20, L30
Freq Conv Mode:
Frequency conversion mode, enable output frequency set 50Hz or
60Hz, input frequency is 60Hz or 50Hz, UPS no alarm not battery and bypass abnormal.
Default is Disable.
Float Temp. Compen:
temperature sensor compensation switch, when need toconnect
battery temperature sensor, change the value to enable.
Temp Sensor Select:
temperature sensor type select has two types: NTC and RS485. NTC
for single and short distance. RS485 for multiple and fardistance.
Inter Power Walk in(s):
When UPS systems are in parallel mode. this enables the UPS to
control the interval that each UPS transfers from battery mode to normal mode, which
reduces the impact on the generator or power grid. The value can be 1~200, default
value is 10.
4.3.7.2.
Parallel setting
CAUTION!
Only two UPS systems of this model can be connected in a parallel system.
Parallel ID:
Parallel ID, must modify the ID after setting work mode to parallel mode. The
value can be 1 to 2, default value is 1, maximum allowed value is 2, because only two UPS
systems of this model can be connected in a parallel system.
Содержание L20-IB00
Страница 2: ......
Страница 17: ...9 L20 L30 3 4 Cabinet view Figure 1 Front view Side view of L20 and L30...
Страница 36: ...27 L20 L30 4 3 4 1 Main Click the main block to enter the main data display window...
Страница 38: ...29 L20 L30 4 3 4 4 Battery Click the battery block to enter the battery data display window...
Страница 39: ...30 L20 L30 4 3 4 5 Status info Click the Status info to enter the Status info display window...
Страница 40: ...31 L20 L30...
Страница 58: ...49 L20 L30 4 3 8 Maintenance Touch correction and battery self test...
Страница 60: ...51 L20 L30 4 3 8 4 Cycle mode Modify the check date time and check time 10S default 10min EOD...
Страница 64: ...55 L20 L30...
Страница 81: ......