Connecting the Inverter to AC Grid
For connecting the inverter to AC grid, use a 1–10 mm
2
cable.
For more wiring information, refer to the
SolarEdge Recommended AC
Wiring Application Note, available on the SolarEdge website at
http://www.solaredge.com/files/pdfs/application-note-recommended-
To connect to AC grid:
1. Turn off the AC circuit breaker on the distribution panel.
2. Strip 2.5'' / 60 mm of the external cable insulation and strip 0.6'' / 15 mm of the
internal wire insulation.
Figure 11: Insulation Stripping – AC Cable
3. Pass the AC cable through the conduit.
4. Connect the wires to the AC terminals as shown below.
Figure 12: AC connection
Connecting the DC Strings to the Inverter
Connect the string to the DC input pairs. If required, connect additional strings in
parallel using an external combiner box/branch cables before connecting to the
inverter.
Single Phase Energy Hub Inverter MAN-01-00812-1.1
32
Connecting the Inverter to AC Grid