74
© Solarbayer GmbH [210205]
Other fault possibilities
Cause
Remedy
Short burning time
Incorrect or fuel with too low a
heating value (e.g. softwood).
Use allowable fuel or
hardwood.
The delivery pressure (chimney
draft) is too high.
Service call.
Boiler pulse
Too much heating gas that can't
be burned and removed.
Check fuel dimensions.
Service call.
False air intake
Check the tightness of the
test openings and doors.
If there's a leak, Service
call.
Buffer tank charging too long
The boiler power is too small for
the application.
Service call.
The hydraulics are faulty.
Service call.
The heating behavior is faulty.
Adapt heating behaviour
to heat demand.
In the chimney condensate forms
too much.
The
chimney
insulation
is
insufficient.
Service call.
The exhaust receiver or system is
not tight.
Check test openings and
exhaust gas connection
and seal.
cracks in the chimneys
The components contain a
certain amount of residual water.
(Note: low edge removal, surface
removal, crack formation etc.
does not lead to any malfunction
and therefore does not constitute
a warranty claim.)
For wide cracks or broken
pieces that reach down to
the boiler construction:
Service call.
Fault reports and their elimination