18
Firmware-Update
Whether the device is in bootloader mode, is indicated by the flashing of the status LED, or it is shown in GBL_
Conf.exe, after a renewed device search, with the appendix „BOOT-LDR“ after the device name. In bootloader
mode the program GBL_Conf.exe can disable the password and the IP ACL, perform a firmware update, and resto-
re the factory settings.
Note
Activation of the bootloader mode and an abandonment of the bootloader does not change the state
of the power or output ports as long as the supply voltage is maintained.
5�1�2
Abandonment of the Bootloader Mode
Via push button
•
Hold both buttons for 3 seconds (only if the device has 2 buttons).
or
•
Remove and connect the power supply without operating a button.
By Software
•
Start GBL_Conf.exe.
•
Do a network search with the „Search“ menu action.
•
In menu „Program Device“ activate the item „Enter Firmware“.
5�1�3
Factory Reset
If the device is in bootloader mode, it can always be put back to its factory default. All TCP / IP settings are reset in
this operation.
Via push button
•
Activate the Bootloader Mode of the device.
•
Hold down the button (or the „Select“ button for devices with 2 buttons) for 6 seconds. If the push button is
recessed, use a pin or paper clip.
•
The status LED will blink in a fast rhythm, please wait until the LED blinks slowly (about 5 seconds).
By Software
•
Activate the Bootloader Mode of the device.
•
Start GBL_Conf.exe.
•
In menu „Program Device“ activate the item „Reset to Fab Settings“.
•