Chapter 9 - Appendix
Version EN-112021-1.30.3
69
9. Make sure that the redundancy link interface cable is connected before plugging in the power terminal
block.
If the replaced FG-200 is powered while the serial link is missing, it will behave like an independent,
non-redundant primary device. If in this case the FG-200 has a valid (possibly unknown) configuration,
it might use H1 node addresses which are already in use on the H1 links. This will disturb or interrupt
communication and application processing on the H1 links.
10. Plug in the power terminal block. The boot process and the download of the configuration
information take about 1 minute. For indication of proper operation as a secondary device refer to
.
57