6.5
Configuration
Note
Settings performed on the web interface are not automatically transferred from the primary
to the secondary FG-200. The secondary FG-200 must also be configured separately.
6.5.1
Settings
6.5.1.1 General Settings
Enable automatic VCR Creation
If this feature is activated, the FG-200 establishes the VCR connection by itself.
Examples:
§
Softing Communication Configuration Tool ComConf: activate
§
Emerson AMS™ Software: activate
§
NI-FBUS Configuration Tool: deactivate
Note
The feature
Enable automatic VCR Creation
has to be activated when the tool comConf is to
be used for the Foundation fieldbus configuration.
Display Blocks
This feature enables or disables the
functionality.
Hint
The use of the point pages creates a lot of traffic of the FF-H1 network. If you do not use this
Monitor feature then you can save more H1 bandwidth and faster reaction time over
Modbus.
35
Содержание FG-200 HSE/FF
Страница 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Страница 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Страница 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Страница 76: ...FG 200 HSE FF Modbus User Manual 76 Version EN 112021 1 30 3 10 ATEX Type Examination Certificate...
Страница 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Страница 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Страница 79: ...Chapter 11 UL Certificate of Compliance Version EN 112021 1 30 3 79 11 UL Certificate of Compliance...
Страница 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...