Chapter 3 - Installation
Version EN-112021-1.30.3
17
Note
As indicated in the connection diagram, the power can be applied alternatively by a special
DIN rail connector (Rail Power Supply). For further information contact Softing Industrial
Automation.
3.1.5
Installation positions
The FG-200 HSE/FF Modbus can be mounted horizontally and vertically. Depending on the installation
position, different ambient operating temperatures (T
a
) are allowed.
Minimum distance
Provide a minimum distance of 50 mm to the air inlet and air outlet to ensure natural
convection.
Rotated installation position
The maximum permissible ambient temperature values also apply to a 180° rotated
installation position.
Horizontal installation position
Maximum ambient temperatures for the FG-200 HSE/FF Modbus
Number of PA
channels used
Maximum fieldbus
voltage
Minimum distance
Maximum permissible
ambient temperature T
a
4
32VDC
0 mm
55 °C
2
24VDC
0 mm
60 °C
4
32VDC
17.5 mm
65 °C
2
24VDC
17.5 mm
70 °C
Содержание FG-200 HSE/FF
Страница 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Страница 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Страница 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Страница 76: ...FG 200 HSE FF Modbus User Manual 76 Version EN 112021 1 30 3 10 ATEX Type Examination Certificate...
Страница 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Страница 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Страница 79: ...Chapter 11 UL Certificate of Compliance Version EN 112021 1 30 3 79 11 UL Certificate of Compliance...
Страница 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...