ELECTRICAL CONNECTIONS
SOFAR 1100...3300TL-G3
39
Removing the connectors
CAUTION
Danger of DC arcing
•
Before removing the plus and minus connector, ensure that
the DC switch has been set to OFF.
In order to remove the plus and minus connection from the inverter,
insert a removal key into the locking and press on the key with the
adequate force as shown in the following illustration:
5.5
Connecting the AC power cables
Connect the inverter to the AC power distributor or the power grid
using AC power cables.
CAUTION
AC connection
•
Each inverter must have its own circuit breaker.
•
Do not connect any consumers between the inverter and
circuit breaker!
•
The AC disconnecting device must be easily accessible.