SOFAR 7K~10.5KTLM-G3
User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 56 -
load reduction.
ID166
LogicIfDerating
Logic interface derating
The inverter is loaded by the execution
logic interface.
ID167
AlarmAntiReflux
Anti reflux derating
The inverter is implemented to prevent
countercurrent load drop.
ID169
FanFault1
Fan 1 fault
Please check whether the fan 1 of
inverter is running normally.
ID170
FanFault2
Fan 2fault
Please check whether the fan 2 of
inverter is running normally.
ID171
FanFault3
Fan 3 fault
Please check whether the fan 3 of
inverter is running normally.
ID172
FanFault4
Fan 4 fault
Please check whether the fan 4 of
inverter is running normally.
ID173
FanFault5
Fan 5 fault
Please check whether the fan 5 of
inverter is running normally.
ID174
FanFault6
Fan 6 fault
Please check whether the fan 6 of
inverter is running normally.
ID175
FanFault7
Fan 7 fault
Please check whether the fan 7 of
inverter is running normally.
7.2. Maintenance
Inverters generally do not need any daily or routine maintenance. Heat sink
should not be blocked by dust, dirt or any other items.Before the cleaning, make
sure that the DC SWITCH is turned OFF and the circuit breaker between
inverter and electrical grid is turned OFF. Wait at least for 5 minutes before the
Cleaning.
Inverter cleaning
Please clean the inverter with an air blower, a dry & soft cloth or a soft bristle
brush. Do NOT clean the inverter with water, corrosive chemicals, detergent,
etc.
Heat sink cleaning
For the long-term proper operation of inverters, ensure there is enough space
around the heat sink for ventilation, check the heat sink for blockage (dust, snow,
etc.) and clean them if they exist. Please clean the heat sink with an air blower, a
dry & soft cloth or a soft bristle brush. Do NOT clean the heat sink with water,
corrosive chemicals, detergent, etc.