3. Safety Parameter
User can modify the Safety Parameter of the machine through the USB flash disk.
And the user needs to create a new folder named 'safety' in the USB flash disk in
advance, and copy the Safety parameter file to be modified to the safety folder.
To enable this function, please contact our company technical
support for more relevant information.
Attention
4. Energy Storage Mode
4.Energy Storage Mode
OK
1.Self-use Mode
OK
2.Time-of-use Mode
3.Timing Mode
4.Passive Mode
OK
Self-use Mode
In Self-use mode, inverter will automatically charge & discharge the battery.
1)
If
PV generation
=
LOAD
consumption (ΔP < 100W) inverter
won’t charge or discharge the
battery.
2)
If
PV
generation
>
LOAD
consumption, the surplus power will
be stored in the battery.
3)
If the battery is full(or already at
Max Charge Power), excess power
will be exported to the grid.
4)
If
PV
generation
<
LOAD
consumption, it will discharge the
battery to supply power to load.