SOFAR 3K~6KTLM-G2
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 55 -
ID10
IpvUnbalance
Input current is not
balanced
Check the input mode(parallel mode/
independent mode) setting of inverter according
to Section 6.3 (C) 6.Input Mode of this user
manual, If it’s incorrect, change it according to
Section 6.3 (A) 10.Set Input mode of this
manual.
ID11 PvConfigSetWro
ng
Incorrect input
mode
ID12
GFCIFault
GFCI Fault
If the fault occurs occasionally, the possible
cause is that the external circuits are abnormal
occasionally. inverter automatically returns to
normal operating status after the fault is rectified.
If the fault occurs frequently and lasts a long
time, check whether the insulation resistance
between the PV array and earth(ground) is too
low, then check the insulation conditions of PV
cable.
ID14
HwBoostOCP
The input current is
too high , and has
happen hardware
protection
Check whether the input current is higher
than the maximum input current of inverters,
then check the input wiring, if both are correct,
please contact technical support.
ID15
HwAcOCP
The grid current is
too high , and has
happen hardware
protection
ID15-ID24 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. Ifno, please contact
technical support.
ID16
AcRmsOCP
The grid current is
too high
ID17
HwADFaultIGri
d
The grid current
sampling error
ID18
HwADFaultDCI The DCI sampling
error
ID19
HwADFaultVGr
id
The grid voltage
sampling error
ID20 GFCIDeviceFaul
t
The GFCI sampling
error
ID21
MChip_Fault
The master chip
fault
ID22
HwAuxPowerFa
ult
The auxiliary
voltage error
ID23 BusVoltZeroFaul
t
The bus voltage
sampling error
ID24 IacRmsUnbalanc
e
The Output current
is not balanced
ID25
BusUVP
The bus voltage Is
too low
If the PV array configuration is correct (no
ID05 fault), the possible cause is that the solar
irradiance is too low. inverter automatically
returns to normal operating status after the solar
irradiance returns to normal level.
ID26
BusOVP
The bus voltage Is
too high
ID26-ID27 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID27
VbusUnbalan
The bus voltage is
not balanced