SOFAR 3.3K~12KTL-X
User manual
All rights reserved
©
Shenzhen SOFARSOLAR Co ., Ltd.
- 64 -
low
SOFAR inverter automatically returns to normal operating
status after the solar irradiance returns to normal level.
ID26
BusOVP
The bus
voltage Is too
high
ID26-ID27 are internal faults of SOFAR inverter, turn OFF
the “DC switch”, wait for 5 minutes, then turn ON the “DC
switch”. Check whether the fault is rectified. If no, please
contact SOFAR technical support.
ID27
VbusUnbal
ance
The bus
voltage is not
balanced
ID28
DciOCP
The Dci is too
high
Check the input mode(parallel mode/ independent mode)
setting of SOFAR inverter according to Section 4.5 of this
user manual.
If the input mode is correct, turn OFF the “DC switch”,
wait for 5 minutes, then turn ON the “DC switch”. Check
whether the fault is rectified. If no, please contact SOFAR
technical support.
ID29
SwOCPIns
tant
The grid
current is too
high
Internal faults of SOFAR inverter, turn OFF the “DC
switch”, wait for 5 minutes, then turn ON the “DC switch”.
Check whether the fault is rectified. If no, please contact
SOFAR technical support.
ID30
SwBOCPI
nstant
Ihe input
current is too
high
Check whether the input current is higher than the
maximum input current of SOFAR inverters, then check
the input wiring, if both are correct, please contact SOFAR
technical support.
ID31- ID48 Reserved Reserved
Reserved
ID49
Consistent
Fault_VGri
d
The grid
voltage
sampling value
between the
master DSP
and slave DSP
is not
consistent
ID49-ID55 are internal faults of SOFAR inverter, turn OFF
the “DC switch”, wait for 5 minutes, then turn ON the “DC
switch”. Check whether the fault is rectified. If no, please
contact SOFAR technical support.
ID50
Consistent
Fault_FGri
d
The grid
frequency
sampling value
between the
master DSP
and slave DSP
is not
consistent