Refer to <6.3 Main interface in this manual for specific operation methods.
Please Note:
Anti-Reflux Function = Export Limit function
Reflux Power = Export apprent Power
Hard Anti-Reflux control = Hard Export limit control
Anti-Reflux Control = Soft Export limit control
When Anti-Reflux function is enabled, the reflux power of point of common
coupling (PCC) will be limited to the set Reflux Power limit. Both Hard Anti-Reflux
Control and Anti-Reflux Control can be used together. However, when Hard
Anti-Reflux control is enabled, Anti-Reflux power limit cannot exceed the Hard
Anti-Reflux power limit. If the Anti-reflux power exceeds the Hard Anti-Reflux
power limit, the limit value is reported to trigger the overload protection.
When communication signal with the electricity meter is lost, the output apprent
power of the inverter is limited to the value of soft export limit and does not trigger
fault protection. When Hard anti reflux control is enabled, a loss of communication
with the meter will trigger the inverter into a fault protection state.
Figure 4-
5
wiring method
Connecting Communications Port
SOFAR 3.3K~12KTL-X has two communication interface, RS485
interface, WIFI interface,as shown in the following figure:
Figure 4-6 WIFI/RS485 location map