81
EN
SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
Name of
parameter
group
Name of
parameter
sub-group
Name of
parameter
Default
value
Programmable range
Description
RIDE
THROUGH
MODE
RIDE TROUGH ENABLE
Ride Through
Enable
Enabled
Enabled/Disabled
Enable Ride-Through
mode
VOLTAGE RIDE THROUGH BEHAVIOR
HVR2 Mode
Not
Applicable
Not Applicable/Momentary
Cessation /Mandatory
Operation/Permissive Operation
Behaviour in HV2
region
HVR1 Mode
Momentary
Cessation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in HV1
region
LVR1 Mode
Mandatory
Operation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in LV1
region
LVR2 Mode
Mandatory
Operation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in LV2
region
LVR3 Mode
Momentary
Cessation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in LV3
region
VOLTAGE RIDE THROUGH TIMINGS
HVR2 Time
0s
Not adjustable
Ride-Through time in
HV2 region
HVR1 Time
12.00 s
0.01 ÷ 300
Ride-Through time in
HV1 region
LVR1 Time
20.00 s
0.01 ÷ 300
Ride-Through time in
LV1 region
LVR2 Time
10.00 s
0.01 ÷ 300
Ride-Through time in
LV2 region
LVR3 Time
1.00 s
0.01 ÷ 300
Ride-Through time in
LV3 region
FREQUENCY RIDE THROUGH BEHAVIOR
HFR2 Mode
Not
Applicable
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in HF2
region
HFR1 Mode
Mandatory
Operation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in HF1
region
LFR1 Mode
Mandatory
Operation
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in LV1
region
LFR2 Mode
Not
Applicable
Not Applicable/Momentary
Cessation/Mandatory
Operation/Permissive Operation
Behaviour in LV2
region
FREQUENCY RIDE THROUGH TIMINGS
HFR2 Time
0.16 s
0.01 ÷ 300
Ride-Through time in
HF2 region
HFR1 Time
299.00 s
0.01 ÷ 300
Ride-Through time in
HF1 region
LFR1 Time
299.00 s
0.01 ÷ 300
Ride-Through time in
LV1 region
LFR2 Time
0.16 s
0.01 ÷ 300
Ride-Through time in
LV2 region