SUNSYS PCS2 IM UL Power Conversion System and Storage with Islanding Mode from 33 to 200 kVA - Ref.: IOMSUNPCXX07-EN 01
17. TECHNICAL SPECIFICATIONS
Model
33 TR
66 TR
100 TR
132 TL
200 TL
DC Section
Range of DC operating volt-
age
450 to 825 Vdc without derating
350 to 850 Vdc with derating
Number of power modules
1
2
3
4
6
Maximum discharging
current
A
80
160
240
160 + 160
240 + 240
Maximum recharging
current
A
80
160
240
160 + 160
240 + 240
Battery Section
Lithium, Lead acid,
Vanadium Redox, Generic
Battery
Supported in combination with PMS.
Please contact Socomec for compatibility.
AC Section
Maximum continuous
power
kW
33
66
100
132
200
Maximum continuous
apparent power
kW
33
66
100
132
200
On-grid overload
110% - 30 minutes
Off-grid symmetrical over-
load
110% - 30 minutes
125% - 10 minutes
150% - 30 seconds
Off-grid asymmetrical over-
load (mono phase load)
190% - 30 minutes
215% - 10 minutes
260% - 30 seconds
Not applicable
Nominal voltage (Un)
VAC
480 (3ph + N)
280 (3ph)
Operating voltage range
VAC
423 to 528 (3ph + N)
246 to 308 (3ph)
Active power droop
–0.24 Hz @ nominal kW supplied
+0.24 Hz @ nominal kW absorbed
Reactive power droop:
percentage voltage variation
+3% Vnom @ Load cosfì 0.8 cap. (neg.)
–7% Vnom @ Load cosfì 0.8 ind. (pos.)
+2% Vnom @ Load cosfì 0.8
cap. (neg.)
–7% Vnom @ Load cosfì 0.8
ind. (pos.)
+9% Vnom @ nominal kVAR cap. (neg.)
–11% Vnom @ nominal kVAR ind. (pos.)
+5% Vnom@nominal kVAR
cap. (neg.)
-10% Vnom@nominal kVAR
cap. (pos.)
Rated frequency (Fn)
Hz
60
Operating frequency range
Hz
59.3 to 60.5
Rated current
A
40
80
120
272
412
Maximum current at nomi-
nal voltage
A
60
120
180
408
618
Overcurrent protection
device
50 A - Type D
100 A - Type
D
160 A - Type
D
315 A - Type
C
500 A - Type
C
Off-grid short-circuit current
3-phase (IK3 IEC60909-
0) and phase-phase (Ik2
IEC60909-0)
75 A x 40
ms +
62 A x 60 ms
150 A x 40
ms +
125 A x 60
ms
225 A x 40
ms +
187 A x 60
ms
462 A x 40
ms +
383 A x 60
ms
700 A x 40
ms +
580 A x 60
ms