26
SUNSYS H30-H30i
- Ref.: IOMSUNHMXX04-GB 00
26
5. COMMISSIONING
5.3. Protection autotest procedure
The user can make sure the Interface Protection System is working properly by activating the autotest via the menu
COMMANDS
> AUTOTEST
.
Moreover, this menu can be used to check whether the inverter has been disconnected properly in the event of a discharge to earth
(GFCI Autotest), in the same way as the test for a differential switch.
Before activating the desired test, make sure that the inverter is switched on and supplying power.
You can check whether the following devices have intervened correctly:
Protection
Description
V>
Maximum network voltage limit intervention test (restrictive threshold)
V<
Minimum network voltage limit intervention test (restrictive threshold)
V>>
Maximum network voltage limit intervention test (permissive threshold)
V<<
Minimum network voltage limit intervention test (permissive threshold)
f>
Maximum network frequency limit intervention test (restrictive threshold)
f<
Minimum network frequency limit intervention test (restrictive threshold)
f>>
Maximum network frequency limit intervention test (permissive threshold)
f<<
Minimum network frequency limit intervention test (permissive threshold)
GFCI
Differential current to earth exceeded intervention test