NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
72
EN
Error
Code
Alarm
Message
Possible
Cause
Solution
0X6100
PFC Over Heat
Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether the
vents are blocked.
2. Contact service
personnel.
0X1003
Battery
Disconnected
1. The UPS is not
properly connected
to the external
battery pack(s).
2. The battery/
batteries is (are)
damaged.
1. Check whether
the UPS is properly
connected to the
external battery
pack(s).
2. Contact service
personnel.
If all possible causes are eliminated but the alarm still appears, please
contact your local dealer or customer service.
4. Error code on display and event list.
Error Code
Alarm Message
0x0100
Mains Input Volt Out Range
0x0120
Mains Input Freq Out Range
0x0121
Input relay short
0x0122
Input Fuse Open
0x0277
Bypass relay Fault
0x02B0
Bypass Over Current
0x1001
Battery End Of Discharge
0x1002
Battery Over Charged
0x1003
Battery Disconnected
0x1004
Battery Life time Expired
0x1005
Battery Reversed
0x1012
Battery Test Fail
0x1013
Battery Test In Progress
0x1101
Output Overload Shutdown
0x1109
Output Short Circuit
0x1200
INV Volt Abnormal