NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
59
EN
Battery
Setup Item
Selectable Value
Default Value
Automatic Battery Test
From 1 day to 365 days (per step: 1 day)
Disable
Deep Discharge Test
20-90% (per step: 10%) 90%
90%
Low Battery Warning
Capacity
0-95% (per step: 5%)
10%
Warning of Remaining Time 0-60mins (per step: 1min)
2mins
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240mins (per step: 1min)
Disable
Charge Mode
2-stage/ 3-stage
2-stage
Internal Charging Current For 7K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8A
For 11K: 1/ 2/ 3/ 4/ 5/ 6A
1A (7K)
2A (11K)
External Battery Source *
Standard battery pack/
Customer own batt. pack
Standard battery pack
External Battery Type
Li battery / Lead Acid / Others (custom)
Lead Acid
External Battery Capacity
Li battery:
Rated Voltage, Total Capacity
Standard battery pack:
Model Name, Quantity
Customer own batt. pack:
Voltage/Qty, Total capaciy
(1/2/3…/999 Ah, one step: 1Ah)
Standard battery pack:
Model Name:
B7000 (7K)
B11000 (11K)
Quantity: 0
Float Charging Voltage
For Lead-Acid Battery:
Option1: Auto/Customize
Option2: (2.20 - 2.35 V/cell, one step: 0.01V)
For Li-ion Battery or Others:
150 - 310 Vdc, one step: 1V
Auto
EOD Voltage
For Lead-Acid Battery:
9.5-11Vdc/Pcs, one step: 0.1V
For Li-ion Battery or Others:
114 - 242 Vdc, one step: 1V
Auto
Install date
YYYY/ MM/ DD
*: When the External Battery Source is set as Standard battery pack, you need
to configure the Part Number and the Quantity of the standard battery pack(s).
When the External Battery Source is set as Customer own batt. pack, the Part
Number and Quantity will be changed accordingly to Battery Voltage and Total
Capacity.