MASTERYS IP+
40-60 kVA 3/1
IT
ALIANO
ENGLISH
36
IOMMASIPXX07-GB 02
COMMUNICATION
9
9.1 MULTILEVEL COMMUNICATION.
MASTERYS™ is able to manage a variety of serial, contact and Ethernet communication channels simultaneously.
The various PCBs and signalling accessories are inserted in the two standard communication slots. This gives MAS-
TERYS™ immediate interfacing and integration fl exibility as soon as the unit is installed with no need for trained
personnel.
The table below lists the possible connections between the communication channels and external devices.
As each channel is independent, simultaneous connections can be made to satisfy the diff erent levels of signalling
and remote monitoring.
See the options paragraph to access the detailed functions of the PCBs installed in the slots.
Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.
Only one card of a kind can be used.
Communication levels
Slot 1
Slot 2 RS 232/485 RS 232 RJ45 10BT
ADC card
• •
GSS card
• •
NetVision card
•
2
•
2
UniVision pro
• •
4
Remote Panel
•
BMS
•
1
•
1
•
4
Modem
•
3
LAN (ethernet)
•
1
Building Management System.
2
Ethernet adapter with Web/SNMP 10/100Mb functions
(E-service via Web required).
3
For T-service via telephone network.
4
By jbus tunnelling on TCP/IP.
8.1-1
3
4
5
2
1
8
9
7
6
Legend pin RS232/485 C1
1
Not connected
2
RX for RS232
3
TX for RS232
4
Data +
5
GND for RS232
6
Data −
7
Reserved
8
Not connected
9
+12 V
Legend pin Modem C2
1
Reserved
2
RX for RS232
3
TX for RS232
4
Reserved
5
GND for RS232
6
Not connected
7
RTS
8
CTS
9
+12 V