MASTERYS IP+
40-60 kVA 3/1
ENGLISH
IOMMASIPXX07-GB 02
41
COMMUNICATION
9
•
Password
: allows the user to
change the password to access
the html. To authorise access only
to users that have a password. In-
sert the new password and write
it down in case of need.
•
JBUS TCP/IP Port
: used to accept
a JBUS frame through LAN tunnel-
ling .
•
Client JBUS IP address to be au-
thorised
: if a specifi c IP address is
inserted in this box, then only that
address/user will be able to ac-
cess the html pages. If the address
0.0.0.0 is used, all the PCs on the
network will be able to access the
supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all users.
•
Software updating
: if on, allows the supervisor to be updated.
•
Page refresh (sec)
: the page refresh rate can be set.
•
Installation
: text string used to describe the UPS installation site, which is useful if there are more than one
unit connected (this value is inserted in SMS messages or e-mails).
•
NTP Server
: indicates the IP address of the time server to automatically update the date and time on the system.
•
GMT Correction (minutes):
indicates local time and the off set in minutes with respect to the zero meridian of
Greenwich
•
Apply the parameter settings
: restarts the monitoring system with the new settings.