socomec INOSYS LBS Series Скачать руководство пользователя страница 4

4 / 16

Pole connection in series - Configuration raccordement - Conexión de los polos en serie

Grounded systems: in some installation standards, this configuration might not be allowed.
For ungrounded systems, see NEC 690.35 (NEC2008, NEC2011, NEC2014, NFPA70).

 COMPULSORY

For comprehension reason, only one type of connection is 

shown.  As  all  poles  are  independent  and  non  polarized, 

the  pole  connections  in  series  can  be  done  between 

adjacent or non-adjacent poles and on the same or oppo-

site side of the product. The minimum number of pole to 

be connected in series must be as shown below for the 

given technical characteristics. Wire bending space as well 

as spacings have to be according to NEC or relevant ins-

tallation standard. For this, the enclosure dimension might 

have to be increased.

For bridging bar and serial connections not supplied by 

Socomec, thermal effect have to be checked.

For multi-circuit products, the signs 

1

2

 represent 

wiring for each circuit.

2 or more separated circuits can also be connected 

together on the inverter side.

  

For multiple polarity switching (ungrounded systems 

or multiple circuit switching), interphase barrier must 

be installed before energizing

 OBLIGATOIRE

Pour une meilleure compréhension, seul un type de rac-

cordement est décrit. Tous les pôles sont indépendants et 

non polarisés, le raccordement des pôles en série peut 

être réalisé entre pôles adjacents ou non, sur le même côté 

ou le côté opposé du produit. Le nombre minimum de 

pôles à raccorder en série doit correspondre aux indica-

tions ci-dessous pour les caractéristiques techniques 

mentionnées. Le rayon de courbure des câbles ainsi que 

les distances entre conducteurs/parois doivent être selon 

le NEC ou la norme d’installation. Pour cela, la dimension 

minimum du coffret pourrait être augmentée. Pour les 

connexions série entre pôles/barres de pontages non 

fournis par Socomec, les impacts thermiques doivent être 

vérifiés.

Pour les produits multi-circuits, les chiffres 

1

2

 

indiquent le raccordement de chaque circuit.

2 circuits ou plus peuvent aussi être connectés ensemble 

du côté de l’onduleur.

  

Pour la coupure de plusieurs polarités (réseau isolé 

avec coupure du + et – ou coupure de plusieurs circuits), 

les écrans entre phase doivent être installés sur le produit.

 OBLIGATORIO

Para mayor claridad, sólo se describe un tipo de conexión. 

Todos los polos son independientes y sin polarización así 

que la conexión de los polos en serie se puede realizar 

entre polos que están contiguos o no, en el mismo lado o 

en  el  lado  opuesto  del  producto.  El  número  mínimo  de 

polos a conectar en serie debe corresponder a las 

siguientes  indicaciones  para  las  características  técnicas 

mencionadas. El radio de curvatura de los cables y las 

distancias entre las partas activas y pasivas respetar las 

normas de instalación NEC. Por ello, la dimensiones 

mínimas de la envolvente deberían ser aumentadas. Para 

la conexión serie entre  los polos / pletinas de puenteado 

no suministradas por Socomec deben ser verificados los 

efectos térmicos.

Para productos con multi-circuitos, las cifras 

1

2

 y 

representan la conexión de cada circuito.

2 o varios circuitos separados se pueden conectar juntos 

en el lado del inversor.

  

Para cortar varias polaridades (red aislada o corte 

multi-circuitos), se deben instalar los cubrebornes 

en el producto.

1 PV circuit - 1000 VDC

1

 

1

 

 Circuit 1

2

 

 Circuit 2

+

(-)

-

(+)

1

+

(-)

-

(+)

1

+

(-)

+

(-)

Grounded network Floating network

1

+

(-)

+

(-)

+

(-)

+

(-)

Mounting of jumpers - Montage des barres de pontage - Montaje de las pletinas de unión

O

OFF

1 PV circuit - 1000 VDC 1 PV circuit - 1500 VDC Tightening torque

Couple de serrage

Par de apriete

Size

Ref.

Fig.

Ref.

Fig.

1

 

UL

100A / 200A

84090016

A

84090016

A

159.31 lb.in 

18 Nm

13

250A

84090025
84090031

B

IEC 160A / 250A / 315A

-

-

84090016

A

Fig. A

84090016 

L= 

0.35in

 / 9mm 

not for 100A UL

L

84090025   

L= 

1.26in

 / 32mm 

84090031   

L= 

2.04in

 / 52mm

L

1

 

84994221

(1)

Flat - PH 

17.5 lb.in

 / 2 Nm

(1) Not UL certified

Fig. B

1 PV circuit - 1500 VDC

1

 

Grounded network

Floating network

1

+

(-)

+

(-)

1

-

(+)

+

(-)

+

(-)

-

(+)

1

+

(-)

+

(-)

Содержание INOSYS LBS Series

Страница 1: ...doivent tre effectu s que par du personnel qualifi TENSION DANGEREUSE Coupez l alimentation de cet appareil avant d y travailler Utilisez toujours un dispositif de d tection de tension valeur nominale...

Страница 2: ...J8 0 21 5 5 0 21 5 4 0 39 10 0 70 18 Connection terminal F2 Connection terminal F3 0 35 9 0 31 8 0 94 24 0 39 10 1 10 28 0 51 13 1 10 28 0 43 11 0 43 11 0 72 18 5 0 72 18 5 0 72 18 5 0 19 5 0 16 4 0 3...

Страница 3: ...ROPER ELECTRICAL CLEARANCES For applications up to 1500V maintain at least 1 clearance between adjacent power terminal lugs and at least 0 500 clearance between any live part and the device enclosure...

Страница 4: ...r Socomec les impacts thermiques doivent tre v rifi s Pour les produits multi circuits les chiffres 1 2 indiquent le raccordement de chaque circuit 2 circuits ou plus peuvent aussi tre connect s ensem...

Страница 5: ...je de las pantallas de protecci n Ref Nb of poles Position 1 84993222 2P Top and bottom 84993232 3P 1 Flat PZ 2 17 5 lb in 2 Nm Flat PZ 2 17 5 lb in 2 Nm 3 4 1 2 2 Mounting of holding insert Montage c...

Страница 6: ...8 T888 88888888 See I S XXXXXX IND CONT EQ XXX T888 88888888 See I S XXXXXX IND CONT EQ XXX T888 88888888 See I S XXXXXX IND CONT EQ XXX T888 88888888 T888 88888888 Ith 10A A600 Q600 See I S 888888 IN...

Страница 7: ...87 in 200 mm ref 14001020 12 59 in 320 mm ref 14001032 15 74 in 400 mm ref 14001040 7 87 in 200 mm ref 14001020 12 59 in 320 mm ref 14001032 15 74 in 400 mm ref 14001040 2 3 1 Allen size 2 5 26 5 lb...

Страница 8: ...o de un defecto se recomienda realizar las verificaciones mencionadas m s arriba 1 vez cada a o EN This equipment must be installed and serviced only by qualified electrical personnel After the instal...

Страница 9: ...socomec com INOSYS LBS PV DC 100 315A IEC 86Pxxxxx IEC UL 87Pxxxxx 1 IEC 160 250 315A UL 100 200 250A DANGER DANGER PELIGRO ZH 4in 10cm p 14 p 14 p 13 p 13 p 13 p 13 p 13 p 13 p 15 p 15 p 13 p 11 p 1...

Страница 10: ...10 Parallel bridging F3 0 98 25 0 49 12 5 0 41 10 5 2 42 61 5 0 31 8 0 31 8 0 20 5 2 0 20 5 2 1 2 3 4 Inter phase barrier Terminal screens Terminal shrouds Double terminal shrouds 1 2 3 4 Inter phase...

Страница 11: ...49 HEX 39542023 3 2 2 Cu 14 Al 12 8 6 3 10 8 4 2 0 35 40 45 50 4 4 5 5 1 5 6 3 16 160 18 10 1 29 32 5 39543023 3 3 39544023 3 4 1 3 84996xxx p 13 UL 1500V 1 0 500 IEC Ie 1 160A 70mm 120mm 20mm 25mm 1...

Страница 12: ...F 1 PV 1000 VDC 1 PV 1500 VDC Size 1 UL 100A 200A 84090016 A 84090016 A 159 31 lb in 18 Nm 13 250A 84090025 84090031 B IEC 160A 250A 315A 84090016 A 84090016 L 0 35in 9mm 100A UL A L 84090025 L 1 26in...

Страница 13: ...2212 2 84992213 3 1 8499622x 1 84993222 2P 84993232 3P 1 PZ 2 17 5 lb in 2 Nm PZ 2 17 5 lb in 2 Nm 3 4 1 2 2 1 84999012 1 1 8499612x p 11 FASTON 0 25x0 03 in 6 3x0 8 mm V 1 849942xx 1 UL 1 O OFF O OFF...

Страница 14: ...888 88888888 See I S XXXXXX IND CONT EQ XXX T888 88888888 T888 88888888 Ith 10A A600 Q600 See I S 888888 IND CONT EQ XXX T888 88888888 Ith 10A A600 Q600 See I S 888888 IND CONT EQ XXX T888 88888888 1...

Страница 15: ...n 400 mm ref 14001040 2 3 1 2 5 26 5 lb in 3 Nm 3 2 2 X L B G F D L X Size L X 1 65 in 0 08 X 42 mm 2 X External enclosure dimension Dimension ext rieure du coffret mini 1 18 in 30 mm Handle mounting...

Страница 16: ...ZH POS O OFF I ON O OFF I ON 0 1 ON I ON 2 4 1 2 4 1 2 1 2 4 1 2 4 1 2 1 2 4 1 2 4 1 O OFF I ON 1 to 0 OFF O OFF 2 4 1 2 4 1 2 1 2 4 1 2 4 1 2 1 2 4 1 2 4 1 min 1x 0 12 in 3 mm max 2x 0 24 in 6 mm 1x...

Отзывы: