10
COUNTIS E50/E53
- Ref.: 536 419 A
COUNTIS E50/E53
PRÉSENTATION
PRESENTATION - INSTALLATION - PRESENTAZIONE -
PRESENTATIE - PRESENTACIÓN - APRESENTAÇÃO
GB
This energy meter with CT inputs measures
electrical energies (active and reactive) in total
or partial mode. It is equipped with a liquid
crystal digital display which allows you to view
energies, instantaneous powers (P, Q and S),
as well as currents and voltages. It also cal-
culates the power factor over 4 quadrants
and features a connection test and correction
function.
%TMBSHNMRRODBHkBSN
COUNTIS E50
Le
COUNTIS E50
features a pulse output for
metering active energy (0 to 9,999,999 kWh)
or reactive energy (0 to 9,999,999 kvarh).
7KLVSXOVHRXWSXWFDQEHFRQĺJXUHGWRWKH
energy type, the weight (0.1, 1, 10, 100
kWh, kvarh and 1 or 10 MWh, Mvarh) and
the duration (100 ms to 900 ms).
%TMBSHNMRRODBHkBSN
COUNTIS E53
COUNTIS E53
features a communication
function providing an RS485 connection (2 or
3 wire) with JBUS/MODBUS
®
protocol. It also
allows COUNTIS E53 to be operated from a
PC or a PLC. Furthermore, this RS485 com-
munication allows you to manage up to 4 rates,
T1, T2, T3 and T4.
JBUS/MODBUS Tables
File Ref.: FSP 09 49272 - 48503011_E53.pdf
Available for download from the website:
www.socomec.com
General info on JBUS MODBUS
,QDVWDQGDUGFRQĺJXUDWLRQDQ56FRQQHF-
tion allows 31
COUNTIS E53
,
COUNTIS Ci
and
DIRIS
to be interconnected with a PC
or a PLC over up to 1200 metres using the
JBUS/MODBUS
®
protocol.
Recommendations:
We advise using a shielded twisted pair with
general LIYCY-CY type shielding in the fol-
lowing cases:
• long network
• high number of products
• environment subject to interference
If a distance of 1200 m is exceeded and/or
there are more than 31
COUNTIS E53
et
DIRIS
you will need to connect a repeater
(1 track) or a spark-gap (4 tracks) to allow an
additional connection beyond 1200 m. For
further information on connection methodo-
logy, please contact us.
Note:
A 120 ohm resistor must be connected to
the 2 ends of the connection; the resistor
can be found on the additional module.
There are other solutions (modem, TCP-IP,
kAQDNOSHBw/KD@RDBNMRTKSTR
"NLLTMHB@SHNM
communicates using a JBUS/MODBUS
®
protocol, which involves a dialogue within a
master/slave structure.
COUNTIS E53
beha-
ves as a slave.
The communication mode is RTU mode
(Remote Terminal Unit) which uses hexade-
cimal characters of at least 8 bits.
1. Key-pad with 4 dual-function keys (display or pro-
gramming)
2. Backlit LCD display
3. Maximum
4. 4 display quadrants
5. Unit
6. Total/partial mode
7. Communication
8. Rates
N 1
N 2
N n
R = 120
1200 M
R = 120
Programmable
controllers
Other systems
N 1
R = 120
repetor
RS485
0+- -+0
N n
R = 120
1200 M
1200 M
Programmable
controllers
Other systems