SNIJDERS SCIENTIFIC
B.V.
ISO9001 certified by Lloyd’s
Economic Premium ECP01E, March ‘06
Page 8 of 22
Subject to change
4
1
2
3
2
4
1
3
4.2.
Control
With the controller IMAGO 500 it’s possible to set the temperature, humidity and light by
handmode of a program.
The lighting is divided over 4 different contact groups, which can be set independently of each
other, using contact 1 up to and including 4.
The Economic Premium can be switched on by means of the main power on/off-switch (11). The
red switch on the panel is to switch off the present buzzer (13). Light on: buzzer active, light off:
buzzer not active.
The red led (12) indicates when there is an alarm situation. It lights up when the temperature or
humidity deviates 5°C from the setpoint (above as well as below). Standard a potential free contact
is executed at the backside of the cabinet. When there is an alarm situation this contact will switch
and an external alarmsystem will be activated.
The controller allows settings of 50 different programs. Each program can be built up from a total
day/ night cycle, in which different steps, both in the day and nightperiod, can be performed. Each
program can operate continuously or can be repeated a number of times (between 1 and 99).
Note: when the controller hasn’t been touched for 15 minutes, automatically the screensaver
will start up. By pressing a soft key, the screensaver will go off.
4.3.
Display
The display of the controller is fitted with three screens (screens 4-5 are optional):
1.
general screen, which shows the temperature, lightposition, remain cycletime and which program is
working in which step (PG & SG)
2.
the adjusted setpoint of the temperature
3.
the adjusted setpoint of the light
4.
percentage dimming of the light (optional)
5.
quantity CO
2
injection (ppm, optional).
By pushing the key you can scroll to channel 1
(temperature & lightcontacts) and channel 2 (percentage of
light).
The display shows 4 different lightsigns, which have the on/off-
status. Lightsign number 1 belongs to 4 lamps (2 left and 2
rightside of the cabinet), etc. See figure lamps (8), both sides.
front
back