2-5
IInnssttaallllaattiioonn
aanndd
O
Oppeerraattiioonn
22. Remove blue service hose from tank. Remove tank
adapter 1-15080 if used.
23. Identify blue hose leading from bottom of unit. Connect
hose end with anti-blowback valve to blue (liquid) tank
port. Position this hose end at 3 o’clock at the tank.
24. Open red and blue valves on recovery tank.
25. Connect blue service hose from manifold gauge
assembly to tank of virgin refrigerant.
3
3
3
3
Position virgin tank with valve up.
3
3
3
3
For R134a, install supplied tank adapter between tank
valve and blue hose.
26. Open the:
—
Virgin tank valve,
—
Blue service hose hand valve, or coupler (CW), and
—
Blue manifold hand valve.
27. Turn compressor switch ON.
COMPRESSOR ON indicator illuminates and compressor
activates.
28. Turn vacuum/recycle valve to RECYCLE.
Refrigerant flows from virgin tank through
D
Duuaall
33441122
and
into prepared recovery tank.
3
3
3
3
Press mode button until
Tare Weight
is displayed.
Monitor weight on LCD display until desired amount of
virgin refrigerant has been transferred. Refer to
Tank
Full/Empty
in this Chapter.
29. When desired amount of refrigerant has been transferred
into recovery tank, close virgin tank hand valve.
30. Allow recycler to run until 15”Hg vacuum is reached.
Then close blue service hose valve or coupler.
31. Turn vacuum/recycle valve OFF
.
32. Turn compressor switch OFF.
33. Compare recovery tank pressure/temperature
relationship with the chart and bleed off any non-
condensables (air) by pressing PURGE button. Refer to
Purging non-condensable gas
in this chapter.
Содержание Dual 3412
Страница 2: ...ii T Ta ab bl le e o of f C Co on nt te en nt ts s ...
Страница 8: ...viii U Us si in ng g t th hi is s M Ma an nu ua al l ...
Страница 14: ...VI S Sa af fe et ty y I In nf fo or rm ma at ti io on n ...
Страница 26: ...1 12 I In nt tr ro od du uc ct ti io on n ...
Страница 46: ...3 4 M Ma ai in nt te en na an nc ce e ...