9
SenTRI4 fire system
Loop cables
There is a maximum limit
of 2Km loop cable usage
allowed per loop circuit.
This maximum limit is the
sum of the cable used on
main loop circuit, spurs
off main loop circuit, plus
cable runs to all input
/ output lines off loop
powered interface units
installed on the same loop.
There is a further
maximum limit of 100m
cable run allowed per
input/output line off loop
powered interface unit.
The device loop cable carries both data
and power, therefore its selection is
important. Note the following:
In countries where the European
EMC directive is in force, only EMC
Compliant cables are to be used.
The loop cable usage must not
exceed 2Km. This includes the cable
used on main loop and spur circuits.
Single pair cable must be used. It is
NOT permissible to run mixed loops
or outgoing and return pairs in a
multi core cable, due to inadequate
separation and possible electrical
interference problems.
Each core of the loop cable must be
1.5mm
2
cross section area.
the cable screen must be capable of
being earthed at each system device
(outstation).
Red is the preferred cover sheath for
fire applications.
The specified loop circuit cables are
also suitable for wiring master alarm,
auxiliary relay, input/output lines and
mains supply.
Enhanced loop cables
Approved cables for loop wiring
(EMC Compliant)
Draka Firetuf FT120 Enhanced -
FTPLUS2EH1.5RD
(formally Firetuf
FT Plus
)
Datwyler Pyrofil Enhanced
Mineral insulated cable (MICC) to
BS6207:Part 1
Prysmian (previously Pirelli)
FP PLUS
*
Standard loop cables
Approved cables for loop wiring
(EMC Compliant)
AEI Cables
FIRETEC
*
7
Alcatel cable
PYROLON E
*
distributed by Winstonlead
7
BICC Pyrotenax
FLAMESIL FRC
*
Cavicel SpA
FIRECEL SR 114H
*
distributed by Cables Britain
Datwyler Pyrofil Standard *
(previously
LIFELINE
)
Draka Firetuf EMC Standard 1.5mm
2
FTEMC2EH1.5RDR
Draka Firetuf
FTES2EH1.5
(previously
FTZ2E1.5 FIRETUF OHLS
*) fire
resistant data cable
Huber & Suhner
RADOX FR
*
Prysmian (formally Pirelli)
FP200 FLEX
*
Prysmian (formally Pirelli)
FP200 GOLD
*
Raydex
CDT FG950
*
2.5mm² Loop cable (2.5Km loop)
The cable reference for
a 2.5mm
2
loop cable
is similar to 1.5mm
2
cable, for example the
cable reference for a
Draka Firetuf 1.5mm
2
is FTPLUS2EH1.5
and for a 2.5mm
2
it is
FTPLUS2EH2.5, consult
cable supplier.
For cables marked with an * see note on
the next page.
Содержание SenTRI2
Страница 42: ...42 SenTRI Sensors Notes...
Страница 43: ...43 SenTRI4 fire system Notes...