Stulz Driver Manual
Page 13 of 16
FieldServer as a Client
Command
Description
Data Type Signed
Range
Units
C6000
1r1h
Reheat 1 hyteresis
Float
N
0..10
r/w
1r2st
Reheat 2 start temperature
Float
N
0..10
r/w
1r2h
Reheat 2 hysteresis
Float
N
0..10
r/w
1r3st
Reheat 3 start temperature
Float
N
0..10
r/w
1r3h
Reheat 3 hysteresis
Float
N
0..10
r/w
1pwwvs
PWW valve start temperature
Float
N
0..10
r/w
1pwwvpb
PWW valve proportional band
Float
N
0..10
r/w
1dhs
Dehumidification start
Integer
N
0..90
r/w
1dhh
Dehumidification hysteresis
Integer
N
0..90
r/w
1hums
Humidification start
Integer
N
0..90
r/w
1humh
Humidification hysteresis
Integer
N
0..90
r/w
1humsa
Humidification start (analogue)
Integer
N
0..90
r/w
1humpba
Humidification proportional band
Integer
N
0..90
r/w
1gcph
Glycol-pump hysteresis
Float
N
0..10
r/w
Module 2
2comps
Compressor start
Float
N
0..10
r/w
2comph
Compressor hysteresis
Float
N
0..10
r/w
2svst
Suction valve start
Float
N
0..10
r/w
2svpb
Suction valve proportional ban
Float
N
0..10
r/w
2drycst
Drycooler start temperature
Integer
N
0..45
C
r
2r1st
Reheat 1 start temperature
Float
N
0..10
r/w
2r1h
Reheat 1 hyteresis
Float
N
0..10
r/w
2r2st
Reheat 2 start temperature
Float
N
0..10
r/w
2r2h
Reheat 2 hysteresis
Float
N
0..10
r/w
2r3st
Reheat 3 start temperature
Float
N
0..10
r/w
2r3h
Reheat 3 hysteresis
Float
N
0..10
r/w
2dhs
Dehumidification start
Integer
N
0..90
%
r/w
2dhh
Dehumidification hysteresis
Integer
N
0..90
%
r/w
2hums
Humidification start
Integer
N
0..90
%
r/w
2humh
Humidification hysteresis
Integer
N
0..90
%
r/w
2humsa
Humidification start (analogue)
Integer
N
0..90
%
r/w
2humpba
Humidification proportional band
Integer
N
0..90
%
r/w
2gecwvs
GE/CW valve start temperature
Float
N
0..10
r/w
2gecwvpb
GE/CW valve proportional band
Float
N
0..10
r/w
Module 3
3comps
Compressor start
Float
N
0..10
r/w
3comph
Compressor hysteresis
Float
N
0..10
r/w
3svst
Suction valve start
Float
N
0..10
r/w
3svpb
Suction valve proportional ban
Float
N
0..10
r/w
3drycst
Drycooler start temperature
Integer
N
0..45
C
r
3r1st
Reheat 1 start temperature
Float
N
0..10
r/w
3r1h
Reheat 1 hyteresis
Float
N
0..10
r/w
3r2st
Reheat 2 start temperature
Float
N
0..10
r/w
3r2h
Reheat 2 hysteresis
Float
N
0..10
r/w
3r3st
Reheat 3 start temperature
Float
N
0..10
r/w
3r3h
Reheat 3 hysteresis
Float
N
0..10
r/w
3dhs
Dehumidification start
Integer
N
0..90
%
r/w
3dhh
Dehumidification hysteresis
Integer
N
0..90
%
r/w
3hums
Humidification start
Integer
N
0..90
%
r/w
3humh
Humidification hysteresis
Integer
N
0..90
%
r/w
3humsa
Humidification start (analogue)
Integer
N
0..90
%
r/w
3humpba
Humidification proportional band
Integer
N
0..90
%
r/w
3gecwvs
GE/CW valve start temperature
Float
N
0..10
r/w
3gecwvpb
GE/CW valve proportional band
Float
N
0..10
r/w
Module 4
4comps
Compressor start
Float
N
0..10
r/w
4comph
Compressor hysteresis
Float
N
0..10
r/w
4svst
Suction valve start
Float
N
0..10
r/w
4svpb
Suction valve proportional ban
Float
N
0..10
r/w
4drycst
Drycooler start temperature
Integer
N
0..45
C
r
4r1st
Reheat 1 start temperature
Float
N
0..10
r/w
4r1h
Reheat 1 hyteresis
Float
N
0..10
r/w