SMC Sierra Monitor FieldServer FS-8700-125 Stulz Скачать руководство пользователя страница 5

 

Stulz Driver Manual 

Page 5 of 16 

  HARDWARE CONNECTIONS  

The FieldServer is connected to the Stulz device over RS-485 as shown in the connection drawings below. 

NOTE:  Configure the Stulz C6000 according to the 

manufacturer’s instructions. 

C6000 

Device 1

C6000 

Device 2

C6000 Device 

32

...

FieldServer to C6000 

Connection Diagram

FieldServer

Orange/

White

4

 C

O

M

+

      

       GND

Blue/White

+

Brown

 

2.1 

Hardware Connection Tips / Hints  

 

Connect the wire to bus 1 on the Stulz device. Make sure that bus 1 is used as bus 2 is used by 
the device to communicate with its IO devices. 

 

Use shielded twisted pair wire to make connections. 

 

Use terminating resistors. The Stulz device has terminating resistors which are set with a jumper.  

 

Make sure that line is terminated at both ends to ensure maximum communication efficiency. 

 

For C6000 controller information, email Stulz at 

[email protected]

. 

14

13

12

11

10

9

8

7

6

5

4

3

2

1

BUS1H

BUS1L

RS485

+

RS485

-

Detail of Pin Arrangement

Showing Connections

Содержание FieldServer FS-8700-125 Stulz

Страница 1: ...evision 1 01 Document Revision 2 B FieldServer FS 8700 125 Stulz Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured after J...

Страница 2: ...t needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email suppo...

Страница 3: ...ient Side Connection Parameters 7 4 2 Client Side Node Parameters 8 4 3 Client Side Map Descriptor Parameters 8 4 3 1 FieldServer Related Map Descriptor Parameters 8 4 3 2 Driver Specific Map Descript...

Страница 4: ...s supported as the protocol only specifies read capabilities on that unit The Client is configurable to read all information into separate data points and supports writing to selected points as specif...

Страница 5: ...onnection Tips Hints Connect the wire to bus 1 on the Stulz device Make sure that bus 1 is used as bus 2 is used by the device to communicate with its IO devices Use shielded twisted pair wire to make...

Страница 6: ...alues Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Byte Uint16 Uint32 Sint16...

Страница 7: ...eeds to be declared in the Nodes section and the data to be provided to the Clients needs to be mapped in the Map Descriptors section Details on how to do this can be found below NOTE In the tables be...

Страница 8: ...p Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Section 3 Data_Array_Offset Starting loc...

Страница 9: ...gth Scan_Interval sett 1 5 Example comments Data_Array_Name This Data Array is where the data will be stored and to which a write can be performed if it is supported see Appendix A Function These comm...

Страница 10: ...winter start Integer N 0 30 C r w ssat Setpoint Supply Air Temperature Float N 10 35 C r w ssah Setpoint Supply Air Humidity Integer N 0 100 r w ssrt Setpoint Room Temperature Float N 10 35 C r w ssrt...

Страница 11: ...yte 1 Uint16 r m3i25 Module 3 digital in status byte 2 Uint16 r m4i14 Module 4 digital in status byte 1 Uint16 r m4i25 Module 4 digital in status byte 2 Uint16 r m5i14 Module 5 digital in status byte...

Страница 12: ...pressure Bit r 4 not used Bit r 5 not used Bit r 6 not used Bit r 7 not used Bit r sett Setpoint temperature Float N 10 35 C r w seth Setpoint humidity Integer N 10 90 r w year Date Year Integer N 0 9...

Страница 13: ...90 r w 2hums Humidification start Integer N 0 90 r w 2humh Humidification hysteresis Integer N 0 90 r w 2humsa Humidification start analogue Integer N 0 90 r w 2humpba Humidification proportional band...

Страница 14: ...midification start Integer N 0 90 r w 5humh Humidification hysteresis Integer N 0 90 r w 5humsa Humidification start analogue Integer N 0 90 r w 5humpba Humidification proportional band Integer N 0 90...

Страница 15: ...humid Too high alarm Bit r 4 water temp too high alarm Bit r 5 return air temp too low alarm Bit r 6 return air humid Too low alarm Bit r 7 supply air temp too low alarm Bit r err2 Error byte 2 Uint1...

Страница 16: ...Stulz Driver Manual Page 16 of 16 APPENDIX B TROUBLESHOOTING Driver Limitations Only the 9600 baud setting is supported by Stulz devices...

Отзывы: