Model 3600-I IR3 Flame Detector
Page 44 of 66
Appendix A.3. Outputs
Electrical
Interface
There are five output-wiring options. These options must be defined at
the factory per the customer order and cannot be changed at the
customer facility.
for the wiring/terminal diagram for each wiring
option.
Unless otherwise specified, the default is Option 1. The wiring
arrangement is identified on the detector by the part number (see
Section
Option 1:
Power, RS-485, 0-20mA (Sink), Fault I Relay (N.C),
Option 2
: Power, RS-485, 0-20mA (Source) and HART protocol,
Fault Relay (N.O), Alarm Relay, (N.O), (N.C)
Option 3
: Power, RS-485, 0-20mA (Source) and HART Protocol,
Fault Relay (N.O), Alarm Relay (N.O, N.C)
Option 4
: Power, RS-485, Fault Relay (N.C), Auxiliary Relay (N.O),
Alarm Relay, (N.O)
Option 5
: Power, RS-485, Fault Relay (N.O), Auxiliary Relay (N.O),
Alarm Relay, (N.O)
Electrical
Outputs
Dry Contact Relays
Relay Name
Type
Normal
Position
Maximum
Ratings
Alarm
DPST
N.O., N.C.
2A at 30 VDC or
0.5A at 250 VAC
Auxiliary
SPST
N.O.
5A at 30 VDC or
250 VAC
Fault *
SPST
N.C. or N.O
5A at 30 VDC or
250 VAC
Figure 32: Contact Ratings
* In wiring options 3, 5 the relay is normally energized open during
normal operation of the detector. The relay is de-energized close
contact if a fault condition or low voltage situation occurs.
NOTE:
The Fault relay (in wiring options 1, 2, 4) is normally energized
closed during normal operation of the detector. The relay is de-
energized open if a fault condition or low voltage situation occurs.
0-20mA Current Output:
The 0-20mA can be Sink or Source
according to the wiring option source (see
). The
maximum permitted
load resistance is 600Ω.
State
Output
Fault
0 +1 mA
BIT Fault
2 mA±10%
Normal
4 mA±10%
IR
8 mA ±5%
UV
12mA±5%
Warning
16 mA±5%
Alarm
20 mA±5%
Figure 33: 20 mA Current Output