Model 3600-I IR3 Flame Detector
Page 38 of 66
3.2.1 Default Functions Settings
The table below lists the default function configuration supplied with the detector:
Function
Value
Notes
Sensitivity
100/30
Alarm Delay
A
Alarm Latch
No
Auxiliary Relay
No
In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used.
Automatic BIT
Yes
Alarm BIT
No
Auxiliary BIT
No
In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used.
EOL
No
In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used.
Heat Mode
Auto
Heat On
41°F (5°C)
The detector starts heating the window for any
temperature below this value (in degrees
Celsius).
Figure 27: Default Function Values
In order to change the default function use:
P.C with Sierra Monitor software, refer to Manual 777050 for instructions
Handheld unit, refer to Manual 777060 for instructions
USB cable with RS-485 converter (1 meter) part number 794079-5
HART Protocol, refer to Manual 777030 for instructions
3.3
Testing Procedures
This section describes the proof testing procedure for proper operation of the detector. The detector can
be tested using the Manual Built-in-Test or the Sierra Monitor IR3 Fire Simulator
– FS-1100.
The detector performs internal test continuously and automatic BIT test every 15 minutes for more details
refer to
Section
This section includes the following topics:
Automatic BIT Test,
Manual BIT Test,
Testing with Fire Simulator Model FS-1200,
Section
3.3.1 Automatic BIT Test
Check that the indicators show normal conditions. See power up information in