background image

 

Model 3600-I IR3 Flame Detector 

Page 48 of 66 

APPENDIX B. WIRING INSTRUCTIONS 

Appendix B.1. General Instructions for Electrical Wiring 

Follow the instructions detailed in this section for determining the correct wire gauge to be used for the 
installation. 

1.  Use the table below to determine the required wire gauge/size for general wiring, such as 

relay wiring. Calculate the permitted voltage drop with respect to load current, wire gauge and 
length of wires. 

AWG # 

mm2 

Ohm per 100 ft. 

Ohm per 100 m 

26 

0.12 - 0.15 

4.32 

14.15 

24 

0.16 - 0.24 

3.42 

11.22 

22 

0.30 - 0.38 

1.71 

5.60 

20 

0.51 - 0.61 

1.07 

3.50 

18 

0.81 - 0.96 

0.67 

2.20 

16 

1.22 - 1.43 

0.43 

1.40 

14 

1.94 - 2.28 

0.27 

0.88 

12 

3.09 - 3.40 

0.17 

0.55 

10 

4.56 - 6.64 

0.11 

0.35 

Figure 35: Maximum DC Resistance at 68°F (20°C) for Copper Wire 

2.  Select wire gauge for power supply wires using the table below. DO NOT connect any circuit 

or load to detectors’ supply inputs. 

o

 

Select 

Number of detectors

 connected in one circuit 

o

 

Select wiring 

Length

 per installation requirements 

o

 

Refer to 

Power Supply Range

 for voltage extreme applied 

Number of 

Detectors 

Recommended Wire Diameter (AWG) 

Power Supply 

Range (VDC) 

24 

18 

16 

14 

22-32 

20 

18 

16 

14 

22-32 

16 

20 

18 

16 

14 

22-32 

12 

20 

18 

16 

14 

20-32 

20 

18 

16 

14 

20-32 

4 and less 

20 

18 

16 

16 

14 

20-32 

Ft (m) 

164 (50) 

328 (100) 

492 (150)  656 (200) 

820 (240) 

 

 

Max. Length from Power Supply to Last Detector 

 

Figure 36: Wiring Length in feet (meters) 

 

 

 

 

Содержание 3600-I

Страница 1: ...Manual T15014 Document Revision A1 Model 3600 I Triple IR IR3 Flame Detector APPLICABILITY EFFECTIVITY Effective for flame detectors manufactured after September 2016...

Страница 2: ...chnology that is protected under one or more issued or pending United States and foreign patents Sierra Monitor and Sentry IT are trademarks of Sierra Monitor Corporation All other trademarks are the...

Страница 3: ...settings Section 3 Operating the Detector how to power up and test the detector also listing safety precautions to take when operating the detector Section 4 Maintenance and Troubleshooting basic main...

Страница 4: ...tional Electrotechnical Commission Explosion IPA Isopropyl Alcohol IR Infrared JP4 Jet Fuel Latching Refers to relays remaining in the ON state even after the ON condition has been removed LED Light E...

Страница 5: ...1 5 6 Detector Status 21 1 5 6 1 Optional Latching 22 1 5 7 Auxiliary Relay as End of Line Resistor 22 1 6 Internal Detector Tests 23 1 6 1 Continuous Feature Test 23 1 6 2 Built In Test BIT 24 1 6 2...

Страница 6: ...cal Wiring 48 Appendix B 2 Typical Wiring Configurations 49 Appendix C RS 485 Communication Network 53 Appendix C 1 RS 485 Overview 53 Appendix D Accessories 54 Appendix D 1 Long Range IR3 Fire Simula...

Страница 7: ...or Test 39 Figure 29 Troubleshooting 41 Figure 30 Detection Range 43 Figure 31 Electrical Specifications 43 Figure 32 Contact Ratings 44 Figure 33 20 mA Current Output 44 Figure 34 Electromagnetic Com...

Страница 8: ...Detector List of Figures Figure 57 Tilt Mount 61 Figure 58 Weather Protector Installed Back View 62 Figure 59 Weather Protector Installed Front View 62 Figure 60 Laser Detection Coverage Pointer 63 F...

Страница 9: ...sily adapted to all environments applications and requirements by changing the detector s configuration parameters Adjusting these parameters as well and performing other maintenance and monitoring ta...

Страница 10: ...el and takes the form 3600X XXXXXX where XXXXXX defines the model according to the above requirements To modify the default or pre ordered configuration and perform maintenance tasks refer to the HART...

Страница 11: ...ault Relay N C Alarm Relay N O Auxiliary N O RS 485 5 Power Manual BIT Fault Relay N O Alarm Relay N O Auxiliary N O RS 485 Figure 3 Wiring Options NOTE Wiring option 1 is a Default The mA sink output...

Страница 12: ...t BIT Manual and Automatic see Section 1 6 2 Heated Window Prevents effects of icing snow and condensation Electrical Interface o Dry contact relays o Communication network RS 485 o 0 20mA output HART...

Страница 13: ...rst sensor is significantly higher than those measured in the second two sensors In order to issue a fire alarm the detector requires that this occurs as well as other conditions for example radiation...

Страница 14: ...ommunication from a network up to 247 detectors to a host computer or universal controller for central monitoring This feature allows for reduced installation costs easy maintenance and local or remot...

Страница 15: ...2 0 1m 2 n heptane pan fire with maximum wind speed of 6 5 ft sec 2 m sec 1 5 1 2 Sensitivity Ranges The detector has four user selectable sensitivity ranges For each range there are two response leve...

Страница 16: ...s 100 sensitivity For fuel fires standard pan fire size 1 ft 2 0 1 m 2 For gas flames 20 inch 0 5m high 8 inch 0 2m width plume fire Maximum Response Time 10 sec Type Of Fuel Percent of Max Distance a...

Страница 17: ...Model 3600 I IR3 Flame Detector Page 17 of 66 1 5 2 Cone of Vision Horizontal 100 Vertical 50 down 45 up Figure 6 Vertical Field of View Figure 5 Horizontal Field of View...

Страница 18: ...s to bright light with snow water rain desert glare and fog IAD Bright colored clothing including red and safety orange IAD Electronic flash 180 watt seconds minimum output IAD Movie light 625 W quart...

Страница 19: ...tector window as shown in Figure 10 The detector statuses are listed in the LED Indications table below Detector Status LED color LED mode Fault BIT Fault Yellow 4 Hz flashing Normal Green 1 Hz flashi...

Страница 20: ...85 Modbus Output Type Wiring Version Detector Status Alarm relay 3600I Options 1XXXX 4XXXX 5XXXX The relay is N C 3600I Options 2XXXX 3XXXX The relay is N O and N C Auxiliary relay 3600I Options 4XXXX...

Страница 21: ...h state the detector activates different outputs as specified in the output signals versus detector state table below Detector State LED Indicator LED Mode Alarm Relay Auxiliary Relay Fault Relay mA o...

Страница 22: ...nual BIT see Section 1 6 2 3 Latching affects the Alarm Relay 0 20mA output the Alarm LED the Auxiliary Relay will be latched only when the programmable function Auxiliary Relay is set to YES NOTE The...

Страница 23: ...ator voltage level Voltage level status of sensor and sensor circuitry for noise or disconnection in the electronic circuitry 0 20mA level output Relays and heater operation Processor Watch dog Softwa...

Страница 24: ...vice versa if the BIT differs from the current status NOTE In BIT Fault status the detector can continue to detect a fire 1 6 2 2 Automatic BIT The detector automatically performs a BIT every 15 minut...

Страница 25: ...3 sec only when the function Alarm BIT is set to YES AUXILIARY relay For wiring options 4 and 5 is activated for 3 sec only when the function Auxiliary BIT is set to YES 0 20mA output Wiring option 1...

Страница 26: ...by RFI and EMI the cable to the detector must be shielded and the detector must be grounded the shield should be grounded at the detector end Spacing and Location The number of detectors and their loc...

Страница 27: ...tor cover for wiring Flat Screw Driver 4 mm Connect ground terminal Flat Screw Driver 2 5 mm Connect wires to the terminal blocks Figure 18 Tools For wiring use color coded conductors or suitable wire...

Страница 28: ...fic chemicals 2 5 Installation Cables Follow the following guideline for the cable installation All cables to the detector must be well shielded in order to comply with EMC requirement see Technical S...

Страница 29: ...or mounted on the Tilt Mount 2 6 1 Tilt Mount Specifications Item Qty Type Location Tilt Mount 1 3600 001 Screw 4 20 UNC x Detector Holding plate Spring Washer 4 No Detector Holding plate Figure 20 US...

Страница 30: ...66 2 6 2 Tilt Mount Assembly Figure 22 shows the Tilt Mount Assembly Figure 23 shows the Tilt Mount Assembly with dimension in both millimeters and inches Figure 22 Tilt Mount Assembly Figure 23 Tilt...

Страница 31: ...ce the detector with its conduit cable entries pointing downwards on the holding plate of the tilt mount Secure the detector with 5 16 18 UNC x 1 screw to the tilt mount 4 Release the Horizontal and V...

Страница 32: ...PT explosion proof conduit connection or M25x1 5 flameproof gland to assemble the cable conduit to the detector 5 Connect the wires to the required terminals on the Terminal Board according to the wir...

Страница 33: ...RS 485 1 11 RS 485 1 RS 485 1 RS 485 1 RS 485 1 RS 485 1 12 RS 485 GND RS 485 GND RS 485 GND RS 485 GND RS 485 GND Figure 25 Model 3600 I IR3 Wiring Options Available with the HART protocol Keep the f...

Страница 34: ...ld is fast and intrinsically safe It enables changing the functions in situations with no need to remove the detector NOTE Sierra Monitor can provide a suitable cable P N 794079 5 with integral RS 485...

Страница 35: ...ions where fast flares may be present The Time Delay for fire alarms in this mode ranges from 2 5 to 15 seconds usually less than 10 seconds 0 3 5 10 15 20 or 30 seconds When an Alarm Detection level...

Страница 36: ...es the Auxiliary Relay for approximately 3 seconds default No Successful Manual Bit does not activate the Auxiliary Relay EOL Yes Auxiliary Relay is used as End of Line No Auxiliary Relay operates in...

Страница 37: ...mode Only perform a Reset when the Latching alarm option has been programmed To reset a detector when in it is in a LATCHED ALARM state Do one of the following o Disconnect power terminal number 1 or...

Страница 38: ...on Values In order to change the default function use P C with Sierra Monitor software refer to Manual 777050 for instructions Handheld unit refer to Manual 777060 for instructions USB cable with RS 4...

Страница 39: ...e detector is exposed to a fire simulator the Alarm and Accessory Relays and 0 20mA are activated during the simulation Therefore automatic extinguishing systems or any external devices which may be a...

Страница 40: ...g window and the reflector of the Flame Detector periodically The frequency of cleaning operations depends upon the local environmental conditions and specific applications The fire detection system d...

Страница 41: ...rrective Action LEDs Off Fault Relay at N O 0 20mA at 0mA No power at the unit Check that the correct power is sent to the detector Check power polarity Check wiring in the detector Send the detector...

Страница 42: ...Model 3600 I IR3 Flame Detector Page 42 of 66 APPENDIX...

Страница 43: ...50 ft 15m to 215 ft 65m Fields of View Horizontal 100 Vertical 95 Built In Test BIT Automatic and Manual Appendix A 2 Electrical Specifications Operating Voltage Status All Outputs Without 0 20mA Pow...

Страница 44: ...er RS 485 Fault Relay N O Auxiliary Relay N O Alarm Relay N O Electrical Outputs Dry Contact Relays Relay Name Type Normal Position Maximum Ratings Alarm DPST N O N C 2A at 30 VDC or 0 5A at 250 VAC A...

Страница 45: ...omputerized controllers The communications protocol is Modbus compatible o This protocol is a standard and widely used o It enables continuous communication between a standard Modbus controller Master...

Страница 46: ...lass I Div 1 Groups B C and D Class II III Div 1 Groups E F and G ATEX IECEx EX II 2 GD EExde IIB H2 T5 75 C T4 85 C Water and Dust Tight NEMA 250 type 6p IP 66 and IP 67 per EN 60529 Electronic Modul...

Страница 47: ...810C method 514 2 procedure VIII Vibration at an acceleration of 1 1g within the frequency range of 5 30 Hz and an acceleration of 3g within the frequency range of 30 500 Hz Mechanical Shock Designed...

Страница 48: ...0 96 0 67 2 20 16 1 22 1 43 0 43 1 40 14 1 94 2 28 0 27 0 88 12 3 09 3 40 0 17 0 55 10 4 56 6 64 0 11 0 35 Figure 35 Maximum DC Resistance at 68 F 20 C for Copper Wire 2 Select wire gauge for power s...

Страница 49: ...erminals 5 8 9 1 3600I 1XXXX Fault Relay N C 0 20mA Sink 0 20mA Sink 2 3600I 2XXXX Fault Relay N C Alarm Relay N C 0 20mA Source 3 3600I 3XXXX Fault Relay N O Alarm Relay N C 0 20mA Source 4 3600I 4XX...

Страница 50: ...Model 3600 I IR3 Flame Detector Page 50 of 66 Figure 40 0 20mA Wiring Option 1 Sink 4 Wire Default Figure 39 Typical Wiring for 4 Wire Controllers Using Option 1 or 2 Wiring...

Страница 51: ...Model 3600 I IR3 Flame Detector Page 51 of 66 Figure 42 0 20mA Wiring Option 1 Unisolated Sink 3 Wire Figure 41 0 2mA Wiring Option 1 Converted to Source 3 Wire...

Страница 52: ...Model 3600 I IR3 Flame Detector Page 52 of 66 NOTE There are no 0 20mA outputs in wiring options 4 and 5 Figure 43 0 2mA Wiring Option 2 3 Source 3 Wire Available with HART Protocol...

Страница 53: ...etectors in an addressable system with four 4 wires only 2 for power and 2 for communication Using repeaters the number of detectors can be much larger 32 detectors for each repeater up to 247 on the...

Страница 54: ...e sequential pattern corresponding to and recognizable by the IR3 detector as fire This allows the IR3 detectors to be tested under simulated fire conditions without the associated risks of an open fl...

Страница 55: ...test and reconnect after simulation To simulate a fire 1 Verify that the optical window is clean 2 Move to the correct distance from the detector according to the type of detector see Appendix D 1 3...

Страница 56: ...arts For any reference to Figure 48 the two additional figures Figure 49 and Figure 50 can be used to see different angles of the same parts the item s reference the same parts for these three figures...

Страница 57: ...counter clockwise 4 Unscrew the locking disc clockwise item 4 Figure 52 5 Pull out the battery item 2 Figure 52 from the Flame Simulator 6 Insert the new battery pack in the simulator housing Only us...

Страница 58: ...Chamber 4 Handle 7 Sight 2 Battery Chamber 5 Reflector 8 Back Cover Locking Screw 3 Battery Back Cover 6 Push Button 9 Laser Diode Figure 51 Flame Simulator General Part Identification Figure 50 Flam...

Страница 59: ...aintenance 1 Ensure the Flame Simulator is charged before operation 2 Ensure the reflector and window are clean 3 Before replacing the battery ensure the replacement Battery Pack is correct P N 380004...

Страница 60: ...that the flame detector is at the correct sensitivity Verify that the flame detector is operating Verify that the flame detector window and or reflector are clean Figure 54 Flame Simulator Troublesho...

Страница 61: ...7 GHz Conducted Disturbances IEC 61000 4 6 10 Vrms 150 kHz to 80 MHz Immunity to main supply voltage variations MIL STD 1275B Figure 55 Flame Simulator Immunity Tests Emission Tests Title Basic Stand...

Страница 62: ...66 Appendix D 3 Weather Protection P N 777163 The weather protector protects the detector from different weather conditions such as snow and rain Figure 58 Weather Protector Installed Back View Figure...

Страница 63: ...etector location and assess the actual coverage of installed detectors The device is universal and can be used with all 3600 Optical Flame Detectors Appendix D 5 Air Shield P N 777161 The Air Shield e...

Страница 64: ...p Alert signal via alarm relay and the fault relay Appendix E 1 2 1 Conditions for Safe Operating 1 The flame detector shall consist only of the approved hardware and software modules 2 The 24V power...

Страница 65: ...nsidered that the contact of the Alarm Relay opens if there is a fire alarm 5 During the forwarding and evaluation of the alarm it must be noted that the relay contact opens NOTE The alarm relay can b...

Страница 66: ...ch original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables i e calibration gases batteries sensors nor to an...

Отзывы: