T
S0700
Kit (Terminal Block)
This kit has a small terminal box inside a junction
box. The electrical entry port {G 3/4} permits connec-
tion of conduit fittings.
SOL.A
1A
(–)
(+)
SOL.B
1B
(–)
(+)
1 station
SOL.A
2A
(–)
(+)
SOL.B
2B
(–)
(+)
2 stations
SOL.A
3A
(–)
(+)
SOL.B
3B
(–)
(+)
3 stations
SOL.A
4A
(–)
(+)
SOL.B
4B
(–)
(+)
4 stations
SOL.A
5A
(–)
(+)
SOL.B
5B
(–)
(+)
5 stations
SOL.A
6A
(–)
(+)
SOL.B
6B
(–)
(+)
6 stations
SOL.A
7A
(–)
(+)
SOL.B
7B
(–)
(+)
7 stations
SOL.A
8A
(–)
(+)
SOL.B
8B
(–)
(+)
8 stations
SOL.A
9A
(–)
(+)
SOL.B
9B
(–)
(+)
9 stations
SOL.A
10A
(–)
(+)
SOL.B
10B
(–)
(+)
10 stations
(+)
(–)
Terminal
no.
Polarity
Electrical Wiring Specifications
COM
Standard wiring
1A
COM
2A
3A
4A
5A
6A
7A
8A
9A
10A
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B
1B
1A
2B
2A
3B
3A
4B
4A
5B
5A
6B
6A
7B
7A
8B
8A
9B
9A
10B
10A
COM
1A
COM
2A
3A
4A
5A
6A
7A
8A
9A
10A
1B
2B
3B
4B
5B
6B
7B
8B
9B
10B
1B
1A
2B
2A
3B
3A
4B
4A
5B
5A
6B
6A
7B
7A
8B
8A
9B
9A
10B
10A
COM
Terminal Block Connection
Proper tightening torque (N·m)
0.7 to 1.2
Mounting screw (M4)
Terminal block cover
Gasket
Electrical entry
2-G3/4
M3 screw
6 mm
Step 3. How to replace terminal block cover
Securely tighten the screws with the torque shown in the table
below, after confirming that the gasket is installed correctly.
Step 1. How to remove terminal block cover
Loosen the 4 mounting screws (M4) and open the terminal
block cover.
Step 2. The diagram below shows the terminal block wiring
schematic. All stations are provided with double
solenoid wiring.
Connect each wire to the power supply side, according
to the markings provided inside the terminal block.
Special Wiring Specifications (Option) [-K]
Mixed single and double wiring are available as an option.
The maximum number of manifold stations is determined by
the number of solenoids. Count one point for a single sole-
noid type and two points for a double solenoid type. The total
number of solenoids (points) must not exceed 20.
1. How to order valves
Indicate an option symbol, -K, for the manifold no. and be
sure to specify the mounting position and number of stations
of the single and double wiring by means of the manifold
specification sheet.
2. Wiring specifications
Connector terminal numbers are connected from solenoid
station 1 on the A side in the order indicated by the arrows
without shipping any terminal numbers.
• Applicable crimp terminal: 1.25-3S,1.25Y-3,1.25Y-3N,1.25Y-3.5
Note)
Double wiring (connected to SOL. A
and SOL. B) is adopted for the internal
wiring of each station, regardless of
valve and option types.
Mixed single and double wiring is avail-
able as an option.
Positive
common
specification
Negative
common
specification
Note) Mounting valve have no
polarity. It can also be used
as a negative common.