SET
CH
kPa
MPa
OUT2
1
2
3
4
OUT1
PRESSURE
Descriptions
UP button
SET button
Unit display
Channel display
DOWN button
kgf/cm
2
bar PSI inHg mmHg
Unit labels
4-digit display
Switch output display
Error Code & Solution
LED display
Contents
Solution
Excess current is
flowing into the
switch output of
OUT1.
Excess current is
flowing into the
switch output of
OUT2.
Supply pressure
exceeds the
maximum regulating
pressure.
Supply pressure is
below the minimum
regulating pressure.
Pressure is applied
to a pressure sensor
during the reset
operation (a zero
point adjustment) as
follows:
When compound
pressure is used:
±
2.5% F.S. or more.
When pressure other
than compound
pressure is used:
±
5% F.S. or more.
∗
After displaying for
2 seconds, it will
return to the
measuring mode.
Shut off the power
supply. After
eliminating the
output factor that
caused the excess
current, turn the
power supply back
on.
Bring the pressure
back to atmospheric
pressure and use
the reset function
(zero point
adjustment) again.
Reduce/Increase
supply pressure to
within the regulating
pressure range.
Shut off the power
supply and turn it
back on. Please
contact SMC if it
does not recover.
Internal Circuit and Connection
PSE200-(M)
• NPN open collector 5 o Auto shift 1 input specification
PSE201-(M)
• PNP open collector 5 o Auto shift 1 input specification
+
–
+12 to 24 VDC
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
+
–
+12 to 24 VDC
Load
Load
Load
Load
Load
DC (+) (Brown)
Auto shift input (Yellow)
CH1_OUT1 (Black)
CH1_OUT2 (White)
CH2_OUT1 (Gray)
CH3_OUT1 (Orange)
CH4_OUT1 (Pink)
DC (–) (Blue)
1.2 k
7.3 k
Main circuit
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
DC (+)
Sensor input: +1 to 5 VDC
DC (–)
N.C.
Load
Load
DC (+) (Brown)
Auto shift input (Yellow)
CH1_OUT1 (Black)
CH1_OUT2 (White)
CH2_OUT1 (Gray)
CH3_OUT1 (Orange)
CH4_OUT1 (Pink)
DC (–) (Blue)
1.2 k
7.3 k
Displays the output status of
OUT1 (CH1 to CH4), OUT2
(CH1 only).
Lights up when it is ON.
Use this button to change the
mode or set value.
Use this button to set the mode
or set value.
Use this button to change the
mode or set value.
Displays the selected channel.
The selected unit lights up. Use
unit labels for units other than
MPa and kPa.
Main circuit
Load
Load
Load
Displays the measured
pressure value, content for
each setting, and error code.
Internal data error.
Internal data error.
Internal data error.
Internal data error.
Please contact SMC.