Appendix C.1 SYNC Modbus RTU Mappings to BACnet and Metasys N2
Point Name
BACnet
Object Type
BACnet
Object ID
N2 Data
Type
N2
Address
Boiler Enable/Room Thermostat 1/Stg 1
BV
1
DO
1
Tank Thermostat
BV
2
DO
2
Manual Reset High Limit 1
BI
3
DI
3
Flow Switch 1
BI
4
DI
4
Gas Pressure Switch 1
BI
5
DI
5
Louver Proving Switch 1
BI
6
DI
6
Air Pressure Switch/Flap Vlv 1
BI
7
DI
7
Blocked Drain Switch 1
BI
8
DI
8
Auto Reset High Limit 1
BI
9
DI
9
Flame 1
BI
10
DI
10
Enable/Room Thermostat 1/Stg 1
BI
11
DI
11
Tank Thermostat
BI
12
DI
12
Manual Reset High Limit 2
BI
13
DI
13
Flow Switch 2
BI
14
DI
14
Gas Pressure Switch 2
BI
15
DI
15
Louver Proving Switch 2
BI
16
DI
16
Air Pressure Switch/Flap Vlv 2
BI
17
DI
17
Blocked Drain Switch 2
BI
18
DI
18
Flame 2
BI
19
DI
19
Run-time Contacts
BI
20
DI
20
Alarm Contacts 1
BI
21
DI
21
CH Pump 1
BI
22
DI
22
DHW Pump 1
BI
23
DI
23
Gas Vlv 1
BI
24
DI
24
System Pump
BI
25
DI
25
Run-time Contacts 2
BI
26
DI
26
Alarm Contacts 2
BI
27
DI
27
CH Pump 2
BI
28
DI
28
Gas Vlv 2
BI
29
DI
29
Discrete Inputs 1 - 16
AI
30
AI
30
Discrete Inputs 17 - 32
AI
31
AI
31
Discrete Inputs 33 - 48
AI
32
AI
32
System/Cascade Setpoint
AI
33
AI
33
Cascade Total Power
AI
34
AI
34
Cascade Current Power
AI
35
AI
35
Outlet Setpoint 1
AI
36
AI
36
Outlet Temperature 1
AI
37
AI
37
Inlet Temperature 1
AI
38
AI
38
Flue Temperature 1
AI
39
AI
39
Firing Rate 1
AI
40
AI
40
Boiler 1 Status Code
AI
41
AI
41
Boiler 1 Blocking Code
AI
42
AI
42
Boiler 1 Lockout Code
AI
43
AI
43
Outlet Setpoint 2
AI
44
AI
44
Outlet Temperature 2
AI
45
AI
45
Inlet Temperature 2
AI
46
AI
46
Flue Temperature 2
AI
47
AI
47
Firing Rate 2
AI
48
AI
48
Boiler 2 Status Code
AI
49
AI
49
Boiler 2 Blocking Code
AI
50
AI
50
Boiler 2 Lockout Code
AI
51
AI
51
Configuration
AV
52
AO
52
Coils
AV
53
AO
53