Lochinvar ProtoNode Start-up Guide
Page 52 of 56
System Pump
BI
21
DI
21
DHW Pump 2
BI
22
DI
22
Discrete Inputs 1 - 16
AI
23
AI
23
Discrete Inputs 17 - 32
AI
24
AI
24
Discrete Inputs 33 - 48
AI
25
AI
25
System Cascade Setpoint
AI
26
AI
26
System Pump Speed
AI
27
AI
27
Cascade Total Power
AI
28
AI
28
Cascade Current Power
AI
29
AI
29
Outlet Setpoint
AI
30
AI
30
Outlet Temperature
AI
31
AI
31
Inlet Temperature
AI
32
AI
32
Flue Temperature
AI
33
AI
33
Firing Rate
AI
34
AI
34
Boiler Pump Speed
AI
35
AI
35
Boiler Status Code
AI
36
AI
36
Boiler Blocking Code
AI
37
AI
37
Boiler Lockout Code
AI
38
AI
38
Configuration
AV
39
AO
39
Coils
AV
40
AO
40
0-10 Volt Input/Rate Cmd/SP Cmd
AV
41
AO
41
Tank Setpoint
AV
42
AO
42
Tank Temperature
AV
43
AO
43
Outdoor Temperature
AV
44
AO
44
System Supply Temperature
AV
45
AO
45
System Return Temperature
AV
46
AO
46
Appendix C.7 Power Fin 2.5-5.0 Modbus RTU Mappings to BACnet and Metasys N2
Point Name
BACnet
Object Type
BACnet
Object ID
N2 Data
Type
N2
Address
Boiler Enable/Room Thermostat 1/Stg 1
BV
1
DO
1
Tank Thermostat Cmd
BV
2
DO
2
Manual Reset High Limit 1
BI
3
DI
3
Flow Switch 1
BI
4
DI
4
Gas Pressure Switch 1
BI
5
DI
5
Louver Proving Switch 1
BI
6
DI
6
Blocked Drain Switch 1
BI
7
DI
7
Flame 1
BI
8
DI
8
Enable/Room Thermostat 1/Stg 1
BI
9
DI
9
Tank Thermostat
BI
10
DI
10
Stage 2/Air Pressure Switch
BI
11
DI
11
Air Pres Switch 2/Flap Vlv 2/Flue Vlv
BI
12
DI
12
Run-time Contacts
BI
13
DI
13
Alarm Contacts 1
BI
14
DI
14
CH Pump 1
BI
15
DI
15
DHW Pump 1
BI
16
DI
16
Louver Relay 1
BI
17
DI
17
Gas Vlv 1
BI
18
DI
18
System Pump
BI
19
DI
19
DHW Pump 2/Flue Valve
BI
20
DI
20
Mains Fan 1
BI
21
DI
21
External Spark
BI
22
DI
22
Discrete Inputs 1 - 16
AI
23
AI
23
Discrete Inputs 17 - 32
AI
24
AI
24
Discrete Inputs 33 - 48
AI
25
AI
25
System/Cascade Setpoint
AI
26
AI
26
System Pump Speed
AI
27
AI
27
Cascade Total Power
AI
28
AI
28
Cascade Current Power
AI
29
AI
29
Outlet Setpoint 1
AI
30
AI
30
Outlet Temperature 1
AI
31
AI
31
Inlet Temperature 1
AI
32
AI
32
Flue Temperature 1
AI
33
AI
33