SMC Networks ISE50 Скачать руководство пользователя страница 5

For General Fluids

High Precision Digital Pressure Switch  

Series 

ZSE50F/ISE50

Possible set range

100.0 to 100.0kPa

1.000 to 1.000MPa

Regulating pressure range

100.0 to 100.0kPa

0.1 to 1.000MPa

Specifications

Note
The possible set ranges for types with auto shift function are as follows:

Fluid that will not corrode stainless steel SUS 630 and 304

12 to 24VDC, Ripple (p-p)  10% or less

55mA or less (With no load)

NPN or PNP 2 output (Max. applied voltage 30V (NPN), Max. load current 80mA)

Variable (0 or above)

Fix (3 digits)

2.5ms or less (with chattering prevention function: 24ms, 192ms, 768ms or less)

With short circuit protection

3 1/2 digit LED display (Sampling frequency: 5 times/sec)

2% F.S. 

1 digit or less (With ambient temperature of 25 

3

C)

Green LED (OUT1: Light up when ON), Red LED (OUT2: Lights up when ON)

No-voltage input (solid state switch or reed switch), input 5ms or more

IP65

Operating: 0 to 50

C, Stored: 

10 to 60

C (With no condensation or freezing)

Operating and stored: 35 to 85% RH (With no condensation)

250VAC for 1 min, between all lead wires and enclosure 

2M

 or more (at 50VDC)  between all lead wires and enclosure

10 to 500Hz with 1.5mm amplitude or 98m/s

2

, whichever is smaller

980m/s

 in X, Y, Z directions 3 times each (Not energized)

3%F.S. or less of measured pressure at 25

C in temperature range of 0 to 50

C

Pressure receiving area: Stainless steel SUS 630, Fittings: Stainless steel SUS 304

02: R 1/4, M5 x 0.8    T2: NPT 1/4, M5 x 0.8

5 wire oil proof heavy duty cable (0.15mm

2

)

Approx. 120g (Each including 3m lead wire)

0.2% F.S. 

1 digit or less

0.3% F.S. 

1 digit or less

Output voltage: 1 to 5V 

5% F.S. or less

Output voltage: 1 to 5V 

2.5% F.S. or less

Rated pressure range
Operating pressure range and regulating pressure range

Proof pressure

 

kPa

MPa

kgf/cm

2

bar

psi

mmHg

inHg

Hysteresis mode 

Window comparator mode

Enclosure

Ambient temperature range

Ambient humidity range

Withstand voltage

Insulation resistance

Vibration resistance

Shock resistance

ZSE50F (Compound pressure)

100 to 100kPa

100 to 100kPa

500kPa

0.1

0.001

0.001

0.02

1

0.1

ISE50 (Positive pressure)

0.000 to 1.000MPa

0.100 to 1.000MPa

1.5MPa

0.001

0.01

0.01

0.1


  In case of types with unit conversion function. (Types without unit   

conversion function are fixed to the SI units (KPa or MPa).)

          When a type with analog output is selected.
          When a type with auto shift is selected.
          0.03 to 0.04 psi in psi display.
          Value clear 

0.01psi in psi display.

Function

Various additional functions are available for easy measurement, switch operation and check of measured values suitable for the 
conditions of the measured fluid.

Auto shift function 

Anti-chattering function

Key lock function

Peak hold function

Bottom hold function

Zero out function
Unit conversion (for overseas use) 

Can correct the pressure set point value of switch output according to fluctuations in the primary pressure.

Prevents malfunction due to sudden fluctuations in the primary pressure by adjusting the response time.

The key board operation can be locked to prevent incorrect operation on the operation switch.

Can retain the maximum pressure value displayed during measurement.

Can retain the minimum pressure value displayed during measurement.

The pressure display can be set at zero when the pressure is open to the atmosphere.

Can convert the display value (for overseas use only).

Page 5

Page 16

Note 1) Select and order by specifying the types and models. 

Note 1)   

Note 2) 
Note 3) 
Note 4) 
Note 5) 

Note 1)

Note 2)

Note 3)

Note 4)

Note 1)

Note 1)

Temperature characteristics 

Wetted material

Port size
Lead wire
Weight

Environmental 
resistance

Setting/Display 
resolution

Fluid
Power supply voltage
Current consumption
Switch output
Repeatability

Hysteresis

Response time
Output short circuit protection

Display

Display accuracy
Indication light

Analog output 

Auto shift input

2

Approved

ZSE/ISE  4/21/02 1:15 PM  Page 5

Содержание ISE50

Страница 1: ...tch Applicable for pressure detection with a wide range of fluids by using a stainless steel diaphragm F ISE ZSE High Precision Digital Pressure Switch For General Fluids 50 60 50 60 Series CAT ES100...

Страница 2: ...l diaphragm Extremely low leakage To confirm absorption of work piece with water on the surface e g wet LCD glass plate To measure hydraulic pressure The stainless steel diaphragm prevents direct cont...

Страница 3: ...of load lock ZSE ISE60 F A2 ZSE ISE60 F B2 1 2000 0 1kPa Positive pressure 1 1000 0 001MPa Series ZSE60F ISE60 URJ 1 4 TSJ 1 4 Model Standard thread type Special fittings for the semiconductor industr...

Страница 4: ...s NPN open collector 2 output Analog output NPN open collector 2 output Auto shift input PNP open collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Brack...

Страница 5: ...e Ambient temperature range Ambient humidity range Withstand voltage Insulation resistance Vibration resistance Shock resistance ZSE50F Compound pressure 100 to 100kPa 100 to 100kPa 500kPa 0 1 0 001 0...

Страница 6: ...OUT2 OFF ON OFF ON OFF ON OFF ON Hysteresis mode Window comparator mode Hysteresis mode Window comparator mode P_1 Large pressure and vacuum pressure Large pressure and vacuum pressure Large pressure...

Страница 7: ...output 1k 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC Main circuit Main circuit Main circuit Main circuit Load Load 6 8K 1 2K Brown DC Blue DC Black OUT 1 White OUT 2 Gray Auto shift i...

Страница 8: ...d on the EEPROM When auto shift is used When the primary pressure changes set the auto shift function to Lo The pressure value at this point will be saved as the reference value to correct the pressur...

Страница 9: ...sed the exce ss current turn the power supply back on Bring the pressure back to atmosp heric pressure and try using the zero out function Reduce Increase supply pressure to within the regulating pres...

Страница 10: ...6 4 18 35 3 5 30 8 45 Piping port R NPT 1 4 20 20 2 M3 x 0 5 depth 4 Piping port M5 x 0 8 depth 5 30 2 6 7 1 2 4 15 2 30 2 5 10 7 7 8 Piping port G Piping port 8 45 25 1 14 5 22 10 1 12 4 G 1 4 Serie...

Страница 11: ...utting dimensions for panel mounting Front protection cover 4 5 20 20 45 15 11 5 6 5 4 5 20 40 30 55 1 6 ZS 24 A Bracket A View A A 41 5 41 5 35 45 15 11 5 4 2 4 5 7 2 7 5 22 20 20 40 30 55 1 6 ZS 24...

Страница 12: ...en collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Bracket A Bracket D Panel mount Panel mount Front protection cover Part no ZS 24 A ZS 24 D ZS 24 E Z...

Страница 13: ...to 100kPa 500kPa 0 1 0 001 0 001 0 02 1 0 1 ISE60 Positive pressure 0 000 to 1 000MPa 0 100 to 1 000MPa 1 5MPa 0 001 0 01 0 01 0 1 Possible set range 100 0 to 100 0kPa 1 000 to 1 000MPa Regulating pr...

Страница 14: ...0 3 5 18 35 6 4 27 7 Piping port URJ 1 4 2 6 7 1 2 4 30 2 5 10 7 7 8 15 2 The following items are identical with those of series ZSE50F ISE50 Item Output type Example of internal circuit and wiring Au...

Страница 15: ...thickness of the panel is to 3 2mm Cutting dimensions for panel mounting 41 5 1 6 55 30 40 20 20 A Bracket A ZS 24 A 4 5 20 4 5 6 5 11 5 15 45 View A 41 5 15 11 5 4 2 4 5 7 2 7 5 22 45 View A 20 20 40...

Страница 16: ...sure and operates switch Normal operation Value clear Manual fine adjustment Peak hold Key lock Bottom hold Unit conversion P 14 P 16 P 14 P 15 Set Output mode Res ponse time and Auto Manual mode The...

Страница 17: ...calibration SET Select the manual setting mode as the initial setting mode Press the SET button and hold it unit P_1 or n_1 appears on the display button Increases the set point value button Decrease...

Страница 18: ...neously to skip to RP2 Repeat vacuum and break several times while AIL is displayed The optimum set point value is deter mined automatically Change the vacuum nozzle or other conditions of the work pi...

Страница 19: ...tion returns to the measurement mode Press the SET button at least 2 seconds Release it when the display turns to UnL Press the SET button at least 4 seconds Release it when the display turns to LoC C...

Страница 20: ...ally operated machinery and equipment Compressed air can be dangerous if handled incorrectly Assembly handling or repair of pneumatic systems should be performed by trained and experienced operators 3...

Страница 21: ...ill cause it to break If you believe the lead wire is damaged and likely to cause malfunctions replace it 3 Confirm proper insulation of wiring Make sure that there is no faulty wiring insulation cont...

Страница 22: ...measures to prevent moisture from freezing in circuits when below 5 C since this may cause damage to the O ring and lead to a malfunction The installation of an air dryer is recommended for eliminatin...

Страница 23: ...torque for bracket mounting screw should be 0 98N m or less 1 Do not use in an environment with spattering liquid of oil or solvent 2 In an environment where the body of the switch is exposed to water...

Страница 24: ...RALIA SMC Pneumatics Australia Pty Ltd NEW ZEALAND SMC Pneumatics N Z Ltd EUROPE AUSTRIA SMC Pneumatik GmbH CZECH SMC Industrial Automation CZ s r o DENMARK SMC Pneumatik A S FINLAND SMC Pneumatics Fi...

Отзывы: