1.  Do not drop, or apply excessive impact (980m/s

2

) while 

handing. Although the body of the sensor may not be 
damaged, the internal parts of the sensor could be damaged 
and lead to a malfunction.

2. The tensile strength of the cord is 49N. Applying a greater 

pulling force on it can cause a malfunction. When handling, 
hold the body of the sensor        do not dangle it from the cord.

3. Do not exceed the screw-in torque of 13.6 N

m when installing 

piping. Exceeding this value may cause malfunctioning of the 
sensor.

4. Do not use pressure sensors with corrosive and/or flammable 

gases or liquids.

Warning

Caution

Handling

Warning

Connection

Pressure Source

1. Mounting with panel mount adapter

2. Mounting with brackets

Mount a bracket to the using two M3 x 5L mounting screws 
and install on piping with a hexagon socket cap screws. The 
switch can be installed horizontally depending on the 
installation location.

Caution

Mounting Method

1.  Incorrect wiring can damage the switch and cause a malfun-

ction or erroneous switch output.

2. Turn off  the power before connecting the wires.
3.  Wire separately from power lines and high voltage lines, 

avoiding wiring in the same conduit with these lines. Malfun-
ctions may occur due to noise from these lines. 

4. If a commercial switching regulator is used, make sure that the 

F.G. terminal is grounded.

1. Our pressure switches are CE marked; however, they are not 

equipped with surge protection against lightning. Lightning 
surge countermeasures should be applied directly to system 
components as necessary.

2.  Our pressure switches do not have an explosion proof rating. 

Never use it in the presence of an explosive gas as this may 
cause a serious explosion.

Operating Environment

Warning

The tightening torque for bracket mounting 
screw should be 0.98N

m or less.

1. Do not use in an environment with spattering liquid of oil or 

solvent.

2. In an environment where the body of the switch is exposed to 

water or dust, there is possibility of water or dust invasion of 
the switch through the atmospheric release port. Insert a ø4 
tube (with inside diameter of ø2.5) into the atmospheric 
release port and pipe the other end to a place with no 
spattering water or other liquid. Do not fold or clog the tube or 
the pressure cannot be measured properly.

Atmospheric 
release port

Air tube

To a safe place with 
no water or dust

Confirm that the air tube is inserted to the bottom of the 
atmospheric release port.

Use SMC TU0425 (Material: Polyurethane, O.D.: ø4, I.D: 
ø2.5) as the air tube.

Mounting screw M3 x 5L

Bracket A or D

Panel

Front protection cover (optional)

Panel mounting
adapter A

Panel mounting
adapter B

1. Use of toxic, corrosive or flammable gas.

The materials of the pressure sensor and fittings on the switch 
are SUS630 and SUS304. Do not use toxic or corrosive 
gas
.
The switch is not protected against explosion. Do not use it 
with flammable gas, either.

2. Compatible fluid

 

  The fluid contact areas are SUS630 (pressure sensor) or 

SUS304 (fittings). Use fluid that will not corrode the materials.

(For corrosiveness of fluid, consult the manufacturer of the  

fluid.)

<ZSE60F/ISE60>

Helium leakage test
Helium leakage test is conducted on the welding parts. Use a 
ferrule a ferrule by (Swagelok

 

fittings) as the TSJ fittings and 

packing, ground, etc. by Cajon (VCR

 

fittings) as the URJ fittings. 

If a ferrule, packing or ground by other manufacturers are to be 
used, conduct helium leakage test before using those products.

Warning

20

Approved

Series

ZSE  F/ISE

Pressure Switch Precautions 1

Be sure to read before handling. Refer to pages 17 through 19 for safety instructions and pressure
switch common precautions.

50

60

50

60

ZSE/ISE  4/21/02 1:15 PM  Page 23

Содержание ISE50

Страница 1: ...tch Applicable for pressure detection with a wide range of fluids by using a stainless steel diaphragm F ISE ZSE High Precision Digital Pressure Switch For General Fluids 50 60 50 60 Series CAT ES100...

Страница 2: ...l diaphragm Extremely low leakage To confirm absorption of work piece with water on the surface e g wet LCD glass plate To measure hydraulic pressure The stainless steel diaphragm prevents direct cont...

Страница 3: ...of load lock ZSE ISE60 F A2 ZSE ISE60 F B2 1 2000 0 1kPa Positive pressure 1 1000 0 001MPa Series ZSE60F ISE60 URJ 1 4 TSJ 1 4 Model Standard thread type Special fittings for the semiconductor industr...

Страница 4: ...s NPN open collector 2 output Analog output NPN open collector 2 output Auto shift input PNP open collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Brack...

Страница 5: ...e Ambient temperature range Ambient humidity range Withstand voltage Insulation resistance Vibration resistance Shock resistance ZSE50F Compound pressure 100 to 100kPa 100 to 100kPa 500kPa 0 1 0 001 0...

Страница 6: ...OUT2 OFF ON OFF ON OFF ON OFF ON Hysteresis mode Window comparator mode Hysteresis mode Window comparator mode P_1 Large pressure and vacuum pressure Large pressure and vacuum pressure Large pressure...

Страница 7: ...output 1k 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC 12VDC to 24VDC Main circuit Main circuit Main circuit Main circuit Load Load 6 8K 1 2K Brown DC Blue DC Black OUT 1 White OUT 2 Gray Auto shift i...

Страница 8: ...d on the EEPROM When auto shift is used When the primary pressure changes set the auto shift function to Lo The pressure value at this point will be saved as the reference value to correct the pressur...

Страница 9: ...sed the exce ss current turn the power supply back on Bring the pressure back to atmosp heric pressure and try using the zero out function Reduce Increase supply pressure to within the regulating pres...

Страница 10: ...6 4 18 35 3 5 30 8 45 Piping port R NPT 1 4 20 20 2 M3 x 0 5 depth 4 Piping port M5 x 0 8 depth 5 30 2 6 7 1 2 4 15 2 30 2 5 10 7 7 8 Piping port G Piping port 8 45 25 1 14 5 22 10 1 12 4 G 1 4 Serie...

Страница 11: ...utting dimensions for panel mounting Front protection cover 4 5 20 20 45 15 11 5 6 5 4 5 20 40 30 55 1 6 ZS 24 A Bracket A View A A 41 5 41 5 35 45 15 11 5 4 2 4 5 7 2 7 5 22 20 20 40 30 55 1 6 ZS 24...

Страница 12: ...en collector 2 output Analog output PNP open collector 2 output Auto shift input 22 30 62 70 Option Bracket A Bracket D Panel mount Panel mount Front protection cover Part no ZS 24 A ZS 24 D ZS 24 E Z...

Страница 13: ...to 100kPa 500kPa 0 1 0 001 0 001 0 02 1 0 1 ISE60 Positive pressure 0 000 to 1 000MPa 0 100 to 1 000MPa 1 5MPa 0 001 0 01 0 01 0 1 Possible set range 100 0 to 100 0kPa 1 000 to 1 000MPa Regulating pr...

Страница 14: ...0 3 5 18 35 6 4 27 7 Piping port URJ 1 4 2 6 7 1 2 4 30 2 5 10 7 7 8 15 2 The following items are identical with those of series ZSE50F ISE50 Item Output type Example of internal circuit and wiring Au...

Страница 15: ...thickness of the panel is to 3 2mm Cutting dimensions for panel mounting 41 5 1 6 55 30 40 20 20 A Bracket A ZS 24 A 4 5 20 4 5 6 5 11 5 15 45 View A 41 5 15 11 5 4 2 4 5 7 2 7 5 22 45 View A 20 20 40...

Страница 16: ...sure and operates switch Normal operation Value clear Manual fine adjustment Peak hold Key lock Bottom hold Unit conversion P 14 P 16 P 14 P 15 Set Output mode Res ponse time and Auto Manual mode The...

Страница 17: ...calibration SET Select the manual setting mode as the initial setting mode Press the SET button and hold it unit P_1 or n_1 appears on the display button Increases the set point value button Decrease...

Страница 18: ...neously to skip to RP2 Repeat vacuum and break several times while AIL is displayed The optimum set point value is deter mined automatically Change the vacuum nozzle or other conditions of the work pi...

Страница 19: ...tion returns to the measurement mode Press the SET button at least 2 seconds Release it when the display turns to UnL Press the SET button at least 4 seconds Release it when the display turns to LoC C...

Страница 20: ...ally operated machinery and equipment Compressed air can be dangerous if handled incorrectly Assembly handling or repair of pneumatic systems should be performed by trained and experienced operators 3...

Страница 21: ...ill cause it to break If you believe the lead wire is damaged and likely to cause malfunctions replace it 3 Confirm proper insulation of wiring Make sure that there is no faulty wiring insulation cont...

Страница 22: ...measures to prevent moisture from freezing in circuits when below 5 C since this may cause damage to the O ring and lead to a malfunction The installation of an air dryer is recommended for eliminatin...

Страница 23: ...torque for bracket mounting screw should be 0 98N m or less 1 Do not use in an environment with spattering liquid of oil or solvent 2 In an environment where the body of the switch is exposed to water...

Страница 24: ...RALIA SMC Pneumatics Australia Pty Ltd NEW ZEALAND SMC Pneumatics N Z Ltd EUROPE AUSTRIA SMC Pneumatik GmbH CZECH SMC Industrial Automation CZ s r o DENMARK SMC Pneumatik A S FINLAND SMC Pneumatics Fi...

Отзывы: