Air Dryer
12 Specification for Option T
12-4 How to connect the power supply and signal cable
12 - 2
IDFA Series
IDX-OM-I076
Terminal block
Grommet
Signal cable inlet
Rubber grommet
Power cable inlet
12-4 How to connect the power supply and signal cable
Connect the power cable and signal cable in the following procedures.
1) Take off the front panel.
2) Insert the power cable prepared by the customer into the power cable inlet (with rubber grommet)
and bring the power cable near the terminal block through the base hole.
3) Connect the power cable to the terminal.
4) Insert the signal cable prepared by the customer into the signal cable inlet (with rubber grommet)
and bring the signal cable near the terminal block.
5) Connect the signal cable to the each terminal.
6) Put back the front panel.
12-5 How to re-start the operation
The output of the abnormal signal can be stopped by turning off the switch with light. Remove the
cause of abnormal operation and leave it for 3 minutes or longer after the stopping the operation, and
turn on the switch with light to re-start.
The thermal relay
is still in operation if the output of the abnormal signal is not stopped even after
the switch with light is turned off. Refer to
“5-2. How to reset the thermal relay and high pressure
switch
” in the operation manual, and reset it.
Note) The high pressure switch can also be in operation for IDFA55E-23 and IDFA75E-23.
Front panel
Customer connection side
Terminal connecting screw: M3
Crimping terminal width: 6.5mm and below
Applicable electrical wire: 1.25mm
2
or more
1 2 3
PE
N
L