Air Dryer
6 References
6-1 Specifications
6 - 1
IDFA Series
IDX-OM-I076
6 References
6-1 Specifications
Model
Specification
IDFA22E IDFA37E IDFA55E IDFA75E
Air FlowRate
(ANR)
(Note 1)
At Outlet Pressure Dew
Point of 3
o
C
182 m
3
/h
273 m
3
/h
390 m
3
/h
660 m
3
/h
At Outlet Pressure Dew
Point of 7
o
C
231 m
3
/h
347 m
3
/h
432 m
3
/h
720 m
3
/h
At Outlet Pressure Dew
Point of 10
o
C
254 m
3
/h
382 m
3
/h
510 m
3
/h
822 m
3
/h
R
a
te
d
Cond
itio
n
Operating Pressure
0.7MPa
Inlet Air Temperature
35
o
C
Ambient Temperature
25
o
C
Voltage 230V
50Hz
Operating
Rang
e
Working Fluid
Compressed Air
Inlet Air Temperature
5 to 50
o
C
MIN.Inlet Air Pressure
0.15MPa
MAX.Inlet Air Pressure
1.0MPa
Ambient Temperature
2 to 40
o
C (Relative Humidity of 85% or less)
Electrical
Specification
Power Source
Single Phase AC230V
±
10
%
50Hz (Note4)
Starting Current (Note2)
22A
33.5A
60A
Operating Current (Note2) 4.3A
6.1A
7.9A
Power Consumption (Note2)
760W
1390W
1700W
Circuit Breaker Capacity (Note3)
10A
20A
Noize at 50Hz
50dB
67dB
Condenser
Plate fin tube type with forced air cooling
Corrugated
fin tube type
with forced
air cooling
Refrigerant R407C(HFC)
Refrigerant Charge Quantity
420
±
10g 730
±
10g 550
±
10g 670
±
10g
Air IN/OUT Connection
R1
R1-1/2
R2
Drain Connection (Outside Diameter of Tubing)
10mm
Painting Finish
Melamine baking finish
Colour
Munsell 10Y8/0.5 (Urbanwhite)
Weight
54kg
62kg
100kg
116kg
Note1: The data for m
3
/h (ANR) is referring to the conditions of 20
°
C, 1atm. pressure & relative humidity of
65%.
Note 2: The value is that of operation under rated condition.
Note 3: Install GFCI breaker with sensivity of 30mA.
Note 4: When short period power shortage (including instantly recovered shortage) is recovered, it may take
a longer starting period than usual starting or may not start due to the protective devices.
6-2 Refrigerant with GWP reference
Note:
1. This product is hermetically sealed and contains fluorinated greenhouse gases.
2. See specification table for refrigerant used in the product.