![SMC Networks IDFA22E-23-A Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/smc-networks/idfa22e-23-a/idfa22e-23-a_operation-manuals_1299744016.webp)
Air Dryer
2 Transportation / Installation
2-2 Installation
2
-
2
IDX-OM-I076
IDFA Series
2-2
Installation
2 - 2 - 1
Location
The product should not be used or stored in the circumstances as follows. Those
circumstances will cause not only malfunction but also failures.
Environment where the product is exposed to
rainwater, moisture vapor, salty water, oil and
so on.
Locations where dust or particles are.
Locations where inflammable or explosive gas
are.
Locations where corrosive gas, solvent,
combustible gas are.
Locations that receive direct sunlight or where
radiant heat is generated.
Locations where ambient temperature is
beyond following range:
On-stream: 2 to 40
o
C
Storage: 0 to 50
o
C (when there is no drain
water inside of the piping)
Locations where temperature changes rapidly.
Locations where strong electromagnetic noise
is generated (locations where electromagnetic
field, strong magnetic field, surge is generated)
Circumstances where static electricity is
produced or discharged through the body of the
product.
Locations where strong high frequency wave is
generated.
Locations where danger of thunder is apparent.
Locations by loading on vehicles, marine
vessels, and so on.
Locations whose altitude is higher than 2,000
meters.
Circumstances where strong vibration or impact
are transmitted.
Circumstances where too much force and
weight are put on the body of the product that
causes it to deform.
Circumstances where enough spaces cannot
be taken to do maintenance (in the plant where
the product is operated).
Spaces needed for maintenance
Front
: 600 mm
Rear
: 600 mm
Top
: 600 mm
Right
: 600 mm
Left
: 600 mm
Locations the ventilation grille of the product
can be blocked.
Place where rejection style air of air
compressor or other driers (hot wind) is inhaled.
Condition which has sudden pressure/flow rate
changes.
2 - 2 - 2
Anchorage
The air dryer should be installed on a vibration-free, stable, horizontal flat surface.
Refer to
“Chapter6 6-3 Dimensions” for the dimensions.
This model should be installed using anchor bolts (not included) to prevent shifting during a potential
earthquake (Recommended size of anchor bolt: M12 x 20L 4pieces).
2 - 2 - 3
Air piping
Connection to the inlet and outlet of compressed air should be made removable by using union and
so on.
Pressing the hexagonal fitting with screw wrench and so on, connect the air piping fittings to the
body.
When mounting any part such as an air filter on the fitting at the compressed air inlet or outlet port,
support the part to prevent excessive force from being applied to the product.
Be careful not to let the vibration of the air compressor transmit.