Chapter 3 Serial communication
3.13
Register Map
HRL Series
3-22
A
larm
fl
ag
3
0
Reservation
Alarm given off status
0= Not occurred
1= Occurred
1
Communication error
2
Outside of the ambient temperature range
3
Maintenance alarm
4
Compressor circuit failure
5
Sensor failure
6
Controller failure
7
Compressor inverter error
8
Compressor inverter communication error
9
CH1 pump inverter error
10
CH1 pump inverter communication error
11
CH2 pump inverter error
12
CH2 pump inverter communication error
13
Reservation
14
Reservation
15
Reservation
3.13.7
Data display
The contents selected in the data instruction will be displayed on the
data display 1 to 4.Table below shows the data type which can be
displayed and the range.
No.
Item
Range
0
None
0
1
Ambient temperature
Decimal number : -327.6 to 327.6
℃
Hexadecimal number : F334h to 0CCCh
(0.1
℃
/dig
2
External tuning temperature
Decimal number : -327.6 to 327.6
℃
Hexadecimal number : F334h to 0CCC
(0.1
℃
/dig)
3
CH1 heat exchanger inlet temperature
Decimal number : -327.6 to 327.6
℃
Hexadecimal number : F334h to 0CCCh
(0.1
℃
/dig)
4
Notice for maintenance
Occurrence status of each maintenance
0= Not occurred 1= Occurred
5
Pressure of high pressure refrigerant circuit
Decimal number : -32.76 to 32.76MPa
Hexadecimal number : F334h to 0CCCh
(0.01MPa/dig)
When the external tuning function is OFF, it will be -327.6
℃
(F334h) fixed.
3.13.8
Circulating fluid set temperature
In SERIAL mode, you can set the circulating fluid set temperature of
this product by specifying the circulating fluid set temperature.
If the temperature exceeds the upper limit of the circulating fluid set
temperature range, the circulating fluid set temperature is changed to
the upper limit value. If it is lower than the lower limit, the circulating
fluid set temperature is changed to the lower limit value.