HRX-OM-W069
Chapter 2 Contact input/output communication /Analog output communication
2.3 Contact input signal
HRL Series
2-6
Table 2.3-1
Setting of contact input signal form
No. Indication
Item
Setting and selection
(1)
Input 1
Contact input
signal 1
Contact
type
1
A contact (normally open)
B contact
(normally closed)
Signal
form
1
Alternate
Momentary
Signal
type
[Off]
Disabled
[External Switch]
External switch signal
[Run/Stop]
1
Run/stop signal
[Run]
2
Run signal
(2)
Input 2
Contact input
signal 2
Contact
type
1
A contact (normally open)
B contact
(normally closed)
Signal
form
1
Alternate
Momentary
Signal
type
[Off]
Disabled
[External Switch]
1 External switch signal
[Run/Stop]
Run/stop signal
[Stop]
2
Stop signal
(3)
Input 3
Contact input
signal 3
3
Contact
type
1
A contact (normally open)
B contact
(normally closed)
1 : By default.
2 : This setting assigns “run” signal to “contact input 1” and “stop” signal to “contact input 2”.
3 : The signal form of contact input 3 is “momentary”.
Содержание HRL100-A
Страница 10: ...HRX OM W069 Chapter 1 Read before using 1 4 Touch panel flow HRL Series 1 6...
Страница 55: ......